Knowledge

Recloser

Source 📝

375: 473:
protection, whereas an earth fault can indicate a Line to Ground or Double Line to Ground fault. Reclosers can then apply a fuse burning policy, where they remain closed for a short period to allow fuses on lateral lines to burn, isolating the fault. If the fault is not cleared, the recloser trips open again. This same policy can be used to deliver energy to fault sites to burn the fault off the line. This could be a branch crossing between multiple lines, or fauna (birds, snakes, etc.) coming into contact with the conductors.
690:
current interruptions by the recloser (or circuit breaker). After a pre-determined number of interruptions, the sectionalizer will open, thereby isolating the faulty section of the circuit, allowing the recloser to restore supply to the other non-fault sections. Some modern recloser controllers can be configured to have reclosers operate in sectionalizer mode. This is used in applications where protection grading margins are too small to provide effective protection co-ordination between electrical assets.
203: 482:
this scenario, and the industry best practice is not to reclose on sensitive earth fault. Reclosers with sensitive earth fault protection capable of detecting 500 mA and below are used as a fire mitigation technique, as they provide an 80% risk reduction in fire starts, however they are never to be used as reclosers in this application, only as single shot distributed circuit breakers which allow for sensitivity to verify the existence of these faults.
673:
lighting during an electrical storm. Autorecloser action may result in electronic devices losing time settings, losing data in volatile memory, halting, restarting, or suffering damage due to power interruption. Owners of such equipment may need to protect electronic devices against the consequences of power interruptions and also power surges.
286:. Interrogation and remote operation capabilities allow utilities to aggregate data about their network performance, and develop automation schemes for power restoration. Automation schemes can either be distributed (executed at the remote recloser level) or centralized (close and open commands issued by a central utility 668:
can occasionally see the effects of an autorecloser in action. If the fault affects the customer's own distribution circuit, they may see one or several brief, complete outages followed by either normal operation (as the autorecloser succeeds in restoring power after a transient fault has cleared) or
635:
As a key overcurrent protection element on single phase laterals, a North American network style design. 3 single phase units can be combined into a "Single Triple" arrangement, where single phase reclosing can improve reliability to unfaulted phases during transient fault events. Despite the ability
481:
Sensitive earth fault protection in reclosers is typically set to immediate lockout. This detection of small leakage currents (less than 1 ampere) on a medium voltage line can indicate insulator failure, broken cables or lines coming into contact with trees. There is no merit in applying reclosing to
709:
Victorian utilities responded to the Royal Commission by converting some of their overhead network in high risk areas to underground cable, replacing exposed overhead conductors with insulated cables, and replacing old reclosers with modern ACRs with remote communications to ensure that settings can
649:
Reclosers can be used to protect three phase mining equipment. These devices are occasionally mounted in mobile kiosks that can be moved as the equipment is moved around the mine site. Design complexity of protection equipment is reduced in these applications, as reclosers include all protection and
689:
equipped with a tripping mechanism triggered by a counter or a timer. A sectionalizer is generally not rated to interrupt fault current however it often has a larger Basic Insulation Level, allowing some sectionalizers to be used as a point of isolation. Each sectionalizer detects and counts fault
427:
Reclosers can also address electric power distribution network damage by dividing up the network into smaller sections, possibly at every electric power distribution downstream branch point, which handle much less power than the breakers at the feeder stations, and can be set to trip at much lower
705:
Incorrectly configured or old model reclosers have been implicated in the starting or spread of wildfires. Research into the Australian 2009 Black Saturday Bushfires indicated that reclosers operating as single shot circuit breakers with Sensitive Ground Fault protection configured at 500mA would
531:
Traditional reclosers were designed simply to automate the action of a line crew visiting a remote distribution site to close a tripped circuit breaker and attempt to restore power. With the advanced protection functionality of modern reclosers, these devices are used in a multitude of additional
463:
The primary class of fault type on an overhead distribution network is lightning strike. Lightning surges increase voltage which can cause localised breakdown of insulation, allow arcing over insulators. Reclosers can detect this as an overcurrent or earth fault (depending on the asymmetry of the
357:
based electronic protective relays in the 1980s resulted in increased recloser sophistication, allowing for differing responses to the various cases of abnormal operation or fault on an electric power distribution network. The high-voltage insulation and interrupting devices in modern reclosers
472:
If after the first, swift reclose, the recloser closes onto a fault, it is likely that the fault is a secondary class of fault, vegetation contact or equipment failure. An overcurrent fault would indicate a line to line class fault, which can be confirmed by negative phase sequence overcurrent
672:
If the fault is on an adjacent circuit to the customer, the customer may see several brief "dips" (sags) in voltage as the heavy fault current flows into the adjacent circuit and is interrupted one or more times. A typical manifestation would be the dip, or intermittent black-out, of domestic
270:
At two multiples of the rated current, the recloser's rapid trip curve can cause a trip (off circuit) in as little as 1.5 cycles (or 30 milliseconds). During those 1.5 cycles, other separate circuits can see voltage dips or blinks until the affected circuit opens to stop the fault current.
935: 464:
fault). Lightning surges pass very quickly (reduce in 50ms), so the first reclose can be configured to both trip and reclose quickly. This first reclose allows for interruption of the arcing caused by lightning, but restores the power quickly.
406:
of supply. Using reclosers during a transient fault, for instance, a tree limb blown off a tree during a windstorm that lands on the power line and quickly clear itself as the limb falls to the ground, allows power to be remotely restored.
621:
SWER network design topology is discouraged in modern electrical engineering due to safety reasons, but due to cost savings it is sometimes deployed. Single Phase Reclosers can be used to improve safety on these lines during fault events.
1099: 261:
or foreign objects coming into contact with exposed distribution lines. Consequently, these transient faults can be resolved by a simple reclose operation. Reclosers are designed to handle a brief open-close duty cycle, where
698:
Fire risk is an innate risk of an overhead distribution network. Regardless of the choice of distribution protection switchgear, the fire risk is always higher with overhead conductors than with underground transmission.
266:
can optionally configure the number and timing of attempted close operations prior to transitioning to a lockout stage. The number of reclose attempts is limited to a maximum of four by recloser standards noted above.
399:. These protection solutions present a major problem when restoring power immediately following transient events, because repair crews need to manually reset the circuit breakers or replace fuses cutouts. 1237: 702:
The Victorian Royal Commission into the 2009 bushfires indicated that reclosing must be disabled on high bushfire risk days, however on low risk days it should be applied for reliability of supply.
963: 448:
The basic philosophy of reclosing is to actively consider the fault types and provide an effective response based on probabilities of the detected fault type. Fault currents are sensed by
353:
devices with rudimentary mechanical-protection-relaying capabilities. Modern automatic circuit reclosers are significantly more advanced than the original hydraulic units. The advent of
636:
to lock single phases with a "Single Triple" arrangement during a permanent fault on one phase, the risk of circulating currents is high and typically a 3 phase lockout is implemented.
706:
reduce fire start risk by 80%. Any form of reclosing should be removed on high fire risk days, and reclosing in general should not be applied to detected Sensitive Earth Fault faults.
428:
power levels. Consequently, a single event on the grid will cut off only the section handled by a single recloser, long before the feeder station would notice a problem and cut power.
402:
Alternatively, reclosers are programmed to automate the reset process remotely after a short circuit and allow a more granular approach to service restoration, resulting in increased
1172: 1202:
Abiri-Jahromi, Amir; Fotuhi-Firuzabad, Mahmud; Parvania, Masood; Mosleh, Mohsen (1 January 2012). "Optimized Sectionalizing Switch Placement Strategy in Distribution Systems".
785:
IEC/IEEE International Standard - High-voltage switchgear and controlgear - Part 111: Automatic circuit reclosers for alternating current systems up to and including 38 kV
349:
Reclosers were invented in the mid 1900s in the USA with the earliest reclosers introduced by Kyle Corporation in the early 1940s. Reclosers were originally oil-filled
1013: 595:
Modern Recloser Controllers use ANSI 25 Synchrocheck, 59N Neutral Voltage Displacement, Synchrophasors, ANSI 25A Auto-Synchronisor and other voltage protection
608:
Using Reclosers installed in a Substation where peak fault currents do not exceed the maximum rated interrupting capacity, usually only Rural Substations
271:
Automatically closing the breaker after it has tripped and stayed open for a brief amount of time, usually after 1 to 5 seconds, is a standard procedure.
585:
Centralised Automation requires remote communication through SCADA or otherwise. Distributed Automation can be configured at the Recloser Controller
341:. Low voltage can cause severe damage to electronic equipment. But when a recloser is used, all three phases open, thereby eliminating the problem. 916: 318:
and SCADA functions. The ratings of reclosers run from 2.4–38 kV for load currents from 10–1200 A and fault currents from 1–16 kA.
933:, Montenegro, Alejandro & Ennis, Michael G., "Power distribution system lateral protection and method", issued 2022-04-12 569:
No Reclosing at all. Sensitive Ground Fault (North America) or Sensitive Earth Fault protection pickup at 500 mA removes 80% risk of fire start
419:
when operated remotely, as they can reduce the need of field crews to travel to site to reset devices which have transitioned to lockout.
250:
62271-111/IEEE Std C37.60 and IEC 62271-200 standards. The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.
189: 333:
conversion, when cutouts are used on the wye side and only 1 out of 3 of the cutout fuses open, some customers on the delta side have a
1265: 124: 247: 279: 330: 326: 86: 1076: 1052: 861: 801: 1021: 1260: 314:) interrupters. Controls for the reclosers range from the original electromechanical systems to digital electronics with 997: 900: 1130: 182: 278:, as they are effectively computer controlled switchgear which can be remotely operated and interrogated using 1275: 759:"IEC 62271-111:2019 Automatic circuit reclosers for alternating current systems up to and including 38 kV" 650:
control required to meet the application; which reduces testing and commissioning costs of the equipment.
211: 387:
To prevent electric power distribution network damage, each station along the network is protected with
299: 175: 23: 1158: 227: 52: 38: 830: 1270: 1201: 989: 243: 729: 226:
designed for use on overhead electricity distribution networks to detect and interrupt transient
853: 846: 734: 334: 263: 57: 253:
For overhead electric power distribution networks, up to 80% of faults are transient, such as
681:
Reclosers may cooperate with down-stream protective devices called sectionalizers, usually a
95: 981: 949: 901:
Jeremy Blair, Greg Hathway, and Trevor Mattson of Schweitzer Engineering Laboratories, Inc.
877: 1040: 665: 374: 8: 982: 307: 1044: 1219: 818: 363: 67: 62: 338: 1072: 1048: 993: 910: 857: 797: 416: 315: 283: 138: 47: 31: 1223: 930: 669:
a complete outage of service (as the autorecloser exhausts its maximum 4 retries).
1238:"AusNet Services Bushfire Mitigation Plan for the Electricity Distribution Network" 1211: 789: 739: 437: 254: 163: 793: 724: 449: 388: 239: 115: 105: 1215: 783: 246:, optimized for use as a protection asset. Commercial ACRs are governed by the 143: 133: 110: 77: 1254: 396: 354: 258: 100: 758: 682: 403: 287: 1159:"Distribution Interconnection Handbook | Pacific Gas and Electric Company" 902: 686: 452: 392: 322: 1131:"Victorian Royal Commission into the Black Saturday Bushfires Australia" 321:
On a 3-phase circuit, a recloser is more beneficial than three separate
202: 719: 359: 350: 275: 223: 72: 1071:(9th ed.), New York: McGraw Hill, pp. 18–8 through 18–15, 443: 153: 476: 440:
issues by reconfiguring the electric power distribution network.
303: 148: 431: 467: 903:"Solutions to Common Distribution Protection Challenges" 852:(Second ed.), London: John Wiley and Sons, p.  639:
Single Triple Recloser or Single Phase Recloser System
382: 1066: 845: 242:with integrated current and voltage sensors and a 16:Electricity distribution networks circuit breakers 611:Typically maximum bus fault currents below 16 kA 444:Typical fault conditions and reclosing principles 274:Reclosers are often used as a key component in a 1252: 878:"Auto-Recloser - Safety and Minimising Downtime" 206:Four reclosers on the right side of a substation 1173:"How Do Reclosers Work? Settings and Operation" 1034: 929: 664:Residential customers in areas fed by affected 337:condition, due to voltage transfer through the 477:Sensitive ground fault / sensitive earth fault 290:to be executed by remotely controlled ACRs). 183: 915:: CS1 maint: multiple names: authors list ( 882:Transmission & Distribution Issue 1 2018 693: 676: 631:Single Phase Laterals Overcurrent Protection 493:Dead Time Intervals For Distribution Systems 366:for current interruption and arc quenching. 843: 617:Single Wire Earth Return Network Protection 572:Recloser with SGF/SEF Capability at 500 mA 298:Autoreclosers are made in single-phase and 984:Power Distribution Planning Reference Book 659: 598:Voltage Sensing on both sides of Recloser 578:Smart Grid Distribution Network Automation 190: 176: 653:Recloser in a Kiosk installation format. 710:be adjusted on high bushfire risk days. 432:Reconfiguration and load flow resolution 373: 280:supervisory control and data acquisition 201: 1097: 1039:, Boca Raton: CRC Press, p. 1319, 468:Vegetation contact or equipment failure 395:which turn off power in the event of a 1253: 1100:"Vegetation Conduction Ignition Tests" 979: 964:"Eaton 3 phase autorecloser datasheet" 485: 378:A recloser installed on a rural feeder 1190:The Lineman's and Cableman's Handbook 1125: 1123: 1093: 1091: 1089: 1087: 1069:The Lineman's and Cableman's Handbook 410: 875: 1204:IEEE Transactions on Power Delivery 1037:The Electrical Engineering Handbook 13: 1120: 1084: 645:Mobile Mining Equipment Protection 383:Protection during fault conditions 14: 1287: 1266:Electric power systems components 1098:Marxsen, Dr Tony (15 July 2015). 1067:Edwin Bernard Kurtz, ed. (1997), 788:. February 2019. pp. 1–272. 556:Conventional Recloser Deployment 125:Electric power systems components 496:Typical Setting Range (seconds) 1230: 1195: 1182: 1165: 1151: 1060: 1028: 1006: 526: 415:Reclosers can save significant 973: 956: 942: 923: 894: 869: 837: 776: 751: 293: 1: 1035:Richard C. Dorf, ed. (1993), 988:. Marcel Dekker Inc. p.  745: 238:, ACRs are essentially rated 87:Electric power infrastructure 794:10.1109/IEEESTD.2019.8641507 458: 7: 1261:Electric power distribution 950:"ABB 3 phase Auto Recloser" 713: 604:Substation Circuit Breakers 582:Centralised or Distributed 501:Initial Trip to 1st Reclose 422: 369: 216:automatic circuit reclosers 212:electric power distribution 10: 1292: 1216:10.1109/TPWRD.2011.2171060 1138:royalcommission.vic.gov.au 344: 1242:www.ausnetservices.com.au 694:Fire safety and wildfires 677:Sectionalizer integration 53:Electric power conversion 39:Electric power conversion 1018:www.cooperindustries.com 980:Willis, H. Lee (2004). 730:Spot network substation 660:Autoreclosers in action 517:3rd Trip to 3rd Reclose 509:2nd Trip to 2nd Reclose 417:operational expenditure 848:Electric Power Systems 735:Electrical engineering 625:Single Phase Recloser 559:Conventional Recloser 436:Reclosers can resolve 379: 207: 58:HVDC converter station 1107:www.energy.vic.gov.au 552:Mid-Feeder Protection 377: 358:typically consist of 302:versions, using oil, 205: 96:Electric power system 844:B. M. Weedy (1972), 666:overhead power lines 591:Renewable Connection 565:Fire Risk Mitigation 339:transformer windings 325:. For example, on a 264:electrical engineers 1276:American inventions 1045:1993eeh..book.....D 536: 486:Dead time intervals 364:vacuum interrupters 308:sulfur hexafluoride 535: 411:Remote restoration 380: 208: 68:DC-to-DC converter 63:AC-to-AC converter 1078:978-0-07-036011-2 1054:978-0-8493-0185-8 863:978-0-471-92445-6 803:978-2-8322-4991-8 657: 656: 524: 523: 520:10 to 30 seconds 512:10 to 20 seconds 282:(SCADA) or other 222:) are a class of 200: 199: 139:Grid-tie inverter 48:Voltage converter 32:Power engineering 1283: 1246: 1245: 1234: 1228: 1227: 1199: 1193: 1186: 1180: 1179: 1177: 1169: 1163: 1162: 1155: 1149: 1148: 1146: 1144: 1135: 1127: 1118: 1117: 1115: 1113: 1104: 1095: 1082: 1081: 1064: 1058: 1057: 1032: 1026: 1025: 1020:. Archived from 1010: 1004: 1003: 987: 977: 971: 970: 968: 960: 954: 953: 946: 940: 939: 938: 934: 927: 921: 920: 914: 906: 898: 892: 891: 889: 888: 876:Thompson, Stan. 873: 867: 866: 851: 841: 835: 834: 828: 824: 822: 814: 812: 810: 780: 774: 773: 771: 769: 755: 740:Renewable energy 537: 534: 490: 489: 389:circuit breakers 362:insulation with 360:solid dielectric 255:lightning strike 244:protection relay 240:circuit breakers 230:. Also known as 192: 185: 178: 164:Protective relay 19: 18: 1291: 1290: 1286: 1285: 1284: 1282: 1281: 1280: 1271:Safety switches 1251: 1250: 1249: 1236: 1235: 1231: 1200: 1196: 1187: 1183: 1175: 1171: 1170: 1166: 1157: 1156: 1152: 1142: 1140: 1133: 1129: 1128: 1121: 1111: 1109: 1102: 1096: 1085: 1079: 1065: 1061: 1055: 1033: 1029: 1012: 1011: 1007: 1000: 978: 974: 966: 962: 961: 957: 948: 947: 943: 936: 928: 924: 908: 907: 899: 895: 886: 884: 874: 870: 864: 842: 838: 826: 825: 816: 815: 808: 806: 804: 782: 781: 777: 767: 765: 763:webstore.iec.ch 757: 756: 752: 748: 725:Circuit breaker 716: 696: 679: 662: 529: 504:0 to 5 seconds 488: 479: 470: 461: 450:current sensing 446: 434: 425: 413: 385: 372: 347: 313: 296: 196: 116:Demand response 106:Electrical grid 17: 12: 11: 5: 1289: 1279: 1278: 1273: 1268: 1263: 1248: 1247: 1229: 1210:(1): 362–370. 1194: 1181: 1164: 1150: 1119: 1083: 1077: 1059: 1053: 1027: 1024:on 2011-05-18. 1005: 999:978-0824748753 998: 972: 955: 941: 922: 893: 868: 862: 836: 827:|journal= 802: 775: 749: 747: 744: 743: 742: 737: 732: 727: 722: 715: 712: 695: 692: 678: 675: 661: 658: 655: 654: 651: 647: 641: 640: 637: 633: 627: 626: 623: 619: 613: 612: 609: 606: 600: 599: 596: 593: 587: 586: 583: 580: 574: 573: 570: 567: 561: 560: 557: 554: 548: 547: 544: 541: 528: 525: 522: 521: 518: 514: 513: 510: 506: 505: 502: 498: 497: 494: 487: 484: 478: 475: 469: 466: 460: 457: 445: 442: 433: 430: 424: 421: 412: 409: 384: 381: 371: 368: 346: 343: 311: 295: 292: 284:communications 198: 197: 195: 194: 187: 180: 172: 169: 168: 167: 166: 161: 156: 151: 146: 144:Energy storage 141: 136: 134:Ring main unit 128: 127: 121: 120: 119: 118: 113: 111:Interconnector 108: 103: 98: 90: 89: 83: 82: 81: 80: 75: 70: 65: 60: 55: 50: 42: 41: 35: 34: 28: 27: 15: 9: 6: 4: 3: 2: 1288: 1277: 1274: 1272: 1269: 1267: 1264: 1262: 1259: 1258: 1256: 1243: 1239: 1233: 1225: 1221: 1217: 1213: 1209: 1205: 1198: 1191: 1185: 1174: 1168: 1160: 1154: 1139: 1132: 1126: 1124: 1108: 1101: 1094: 1092: 1090: 1088: 1080: 1074: 1070: 1063: 1056: 1050: 1046: 1042: 1038: 1031: 1023: 1019: 1015: 1014:"Our History" 1009: 1001: 995: 991: 986: 985: 976: 965: 959: 951: 945: 932: 926: 918: 912: 904: 897: 883: 879: 872: 865: 859: 855: 850: 849: 840: 832: 820: 805: 799: 795: 791: 787: 786: 779: 764: 760: 754: 750: 741: 738: 736: 733: 731: 728: 726: 723: 721: 718: 717: 711: 707: 703: 700: 691: 688: 684: 674: 670: 667: 652: 648: 646: 643: 642: 638: 634: 632: 629: 628: 624: 620: 618: 615: 614: 610: 607: 605: 602: 601: 597: 594: 592: 589: 588: 584: 581: 579: 576: 575: 571: 568: 566: 563: 562: 558: 555: 553: 550: 549: 546:Requirements 545: 542: 539: 538: 533: 532:applications 519: 516: 515: 511: 508: 507: 503: 500: 499: 495: 492: 491: 483: 474: 465: 456: 454: 451: 441: 439: 429: 420: 418: 408: 405: 400: 398: 397:short circuit 394: 390: 376: 367: 365: 361: 356: 355:semiconductor 352: 342: 340: 336: 332: 328: 324: 319: 317: 309: 305: 301: 291: 289: 285: 281: 277: 272: 268: 265: 260: 256: 251: 249: 245: 241: 237: 236:autoreclosers 233: 229: 225: 221: 217: 213: 204: 193: 188: 186: 181: 179: 174: 173: 171: 170: 165: 162: 160: 157: 155: 152: 150: 147: 145: 142: 140: 137: 135: 132: 131: 130: 129: 126: 123: 122: 117: 114: 112: 109: 107: 104: 102: 101:Power station 99: 97: 94: 93: 92: 91: 88: 85: 84: 79: 76: 74: 71: 69: 66: 64: 61: 59: 56: 54: 51: 49: 46: 45: 44: 43: 40: 37: 36: 33: 30: 29: 25: 21: 20: 1241: 1232: 1207: 1203: 1197: 1189: 1184: 1167: 1153: 1141:. Retrieved 1137: 1110:. Retrieved 1106: 1068: 1062: 1036: 1030: 1022:the original 1017: 1008: 983: 975: 958: 944: 931:US11303109B2 925: 896: 885:. Retrieved 881: 871: 847: 839: 807:. Retrieved 784: 778: 766:. Retrieved 762: 753: 708: 704: 701: 697: 683:disconnector 680: 671: 663: 644: 630: 616: 603: 590: 577: 564: 551: 543:Methodology 540:Application 530: 527:Applications 480: 471: 462: 453:transformers 447: 435: 426: 414: 404:availability 401: 393:fuse cutouts 386: 348: 323:fuse cutouts 320: 297: 288:control room 273: 269: 252: 235: 231: 219: 215: 209: 158: 335:low voltage 300:three-phase 294:Description 1255:Categories 1192:pp. 18–12. 887:2018-07-02 746:References 720:Smart grid 276:smart grid 224:switchgear 829:ignored ( 819:cite book 459:Lightning 438:load flow 351:hydraulic 232:reclosers 73:Rectifier 1224:47091809 911:cite web 714:See also 423:Division 370:Purposes 316:metering 159:Recloser 154:Bus duct 78:Inverter 24:a series 22:Part of 1188:Kurtz, 1161:. 2017. 1041:Bibcode 809:25 June 768:25 June 687:cutouts 345:History 1222:  1143:3 July 1112:3 July 1075:  1051:  996:  937:  860:  800:  304:vacuum 259:surges 228:faults 149:Busbar 1220:S2CID 1176:(PDF) 1134:(PDF) 1103:(PDF) 967:(PDF) 331:delta 306:, or 1145:2018 1114:2018 1073:ISBN 1049:ISBN 994:ISBN 917:link 858:ISBN 831:help 811:2022 798:ISBN 770:2022 220:ACRs 1212:doi 990:526 790:doi 685:or 391:or 329:to 327:wye 310:(SF 248:IEC 234:or 210:In 1257:: 1240:. 1218:. 1208:27 1206:. 1136:. 1122:^ 1105:. 1086:^ 1047:, 1016:. 992:. 913:}} 909:{{ 880:. 856:, 854:26 823:: 821:}} 817:{{ 796:. 761:. 455:. 257:, 214:, 26:on 1244:. 1226:. 1214:: 1178:. 1147:. 1116:. 1043:: 1002:. 969:. 952:. 919:) 905:. 890:. 833:) 813:. 792:: 772:. 312:6 218:( 191:e 184:t 177:v

Index

a series
Power engineering
Electric power conversion
Voltage converter
Electric power conversion
HVDC converter station
AC-to-AC converter
DC-to-DC converter
Rectifier
Inverter
Electric power infrastructure
Electric power system
Power station
Electrical grid
Interconnector
Demand response
Electric power systems components
Ring main unit
Grid-tie inverter
Energy storage
Busbar
Bus duct
Recloser
Protective relay
v
t
e

electric power distribution
switchgear

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.