Knowledge

Blower door

Source ๐Ÿ“

542:
the less air is needed from the blower door fan to create a change in building pressure. Typically, only depressurization testing is performed, but both depressurization and pressurization are preferable. Different values for blower door metrics are to be expected for pressurizing and depressurizing, due to the building envelope's response to directional airflow. The smallest fan ring that allows the fan to reach the maximum target indoor/outdoor pressure differential should be used. A multi-point test can be performed either manually or using data acquisition and fan control software products. The manual test consists of adjusting the fan to maintain a series of indoor/outdoor pressure differentials and recording the resulting average fan and indoor/outdoor pressures. Alternatively, a single-point test can be performed, where the blower door fan is ramped up to a reference indoor/outdoor pressure differential and the fan pressure is recorded. Often the blower door hardware converts fan pressure measurements directly to fan airflow values.
533:
mechanical exhaust devices in the home, such as bathroom exhaust, kitchen range hood or dryer, should be turned off. Pressure tubing is used to measure the fan pressure, and it is also run to the exterior of the building, so that the indoor/outdoor pressure differential can be measured. The exterior pressure sensor should be shielded from wind and direct sunlight. The test begins by sealing the face of the fan and measuring the baseline indoor/outdoor pressure differential. The average value is to be subtracted from all indoor/outdoor pressure differential measurements during the test.
513: 1298:. These leakage characteristics of the building envelope can then be used to calculate how much airflow will be induced through the building envelope for a given pressure difference caused by wind, temperature difference or mechanical forces. 50 Pa can be plugged into the orifice-flow equation, along with the derived building C and n values to calculate airflow at 50 pascal. This same method can be used to calculate airflow at a variety of pressures, for use in creation of other blower door metrics. 126: 551: 3977: 3248:
Effective Leakage Area assumes that all of the individual leakage areas in the building are combined into a single idealized orifice or hole. This value is typically described to building owners as the area of a window that is open 24/7, 365 in their building. The ELA will change depending on the reference pressure used to calculate it. 4 Pa is typically used in the US, whereas a reference pressure of 10 Pa is used in Canada. It is calculated as follows:
237:'s Division of Building Research (NRC/DBR) in Saskatchewan, advanced the published work of Tamura in 1975 and went from a blower window to a blower door concept used in the construction of the Saskatchewan Conservation House in 1977. The Saskatchewan group was actively involved in the development of the blower door in 1977-78 and published their findings in 1980. They made available their flow nozzle to interested companies including one from Minneapolis. 3985: 29: 2975: 4087:
protected, the presence of continual mixing and clean agent being used will affect the hold time also. The 2008 Edition of NFPA-2001 required a peak pressure evaluation in addition but the industry in the USA in particular has been slow to institute this important requirement since excessive pressure during discharge has damaged many enclosures. This requirement was designed to prevent that.
241:, who had been in Ottawa in 1967 when Tamura was conducting his work, continued to work on blower door technology after Tamura published his paper. Tamura's blower window concept from 1967, preceded the Swedish work in 1977 by a decade. The first blower door was further used to test the airtightness of the Saskatchewan Conservation House built in 1977, which was tested at 0.5  194:, and others in efforts to assess the construction quality of the building envelope, locate air leakage pathways, assess how much ventilation is supplied by the air leakage, assess the energy losses resulting from that air leakage, determine if the building is too tight or too loose, determine if the building needs mechanical 4074:
NFPA standards for equipment calibration are about the same as they are for other types of testing, so any modern blower door equipment is sufficiently accurate to perform NFPA enclosure integrity testing. Specialized software or a tedious calculation must be provided to arrive at the hold time which
1309:
in the analysis and generation of blower door metrics. This method is preferred by some for two main reasons: (1) measuring and recording one data point is easier than recording multiple test points, and (2) the measurements are least reliable at very low building pressure differentials, due both to
541:
The blower door fan is used to blow air into or out of the building, creating either a positive or negative pressure differential between inside and outside. This pressure difference forces air through all holes and penetrations in the building enclosure. The tighter the building (e.g. fewer holes),
252:
These early research efforts demonstrated the potential power of blower door testing in revealing otherwise unaccounted for energy losses in homes. Previously, air leakage around doors, windows and electrical outlets was considered to be the primary leakage pathway in homes, but Harrje, Dutt and Beya
4070:
NFPA-2001 (2015 Edition) is used throughout North America, many Asian countries and the Middle East. A hold time analysis has been required since 1985. ISO-14520-2015 version or EN-15004 Standards are used throughout Europe while FIA Standards are used in the UK. Results from all these standards are
4062:
and FIA standards that also require the test is repeated annually if any doubt exists about the airtightness from the previous test. These types of enclosures are typically server rooms containing large amounts of computer and electronic hardware that would be damaged by the more typical water based
3238:
This normalizes the airflow at a specified building pressure by the building's volume, which allows for more direct comparison of homes of different sizes and layouts. This metric indicates the rate at which the air in a building is replaced with outside air, and as a result, is an important metric
3247:
In order to take values generated by fan pressurization and to use them in determining natural air exchange, the effective leakage area of a building must be calculated. Each gap and crack in the building envelope contributes a certain amount of area to the total leakage area of the building. The
2032:
are referred to as air density correction factors in product literature. They are often tabulated in easy to use tables in product literature, where a factor can be determined from outside and inside temperatures. If such tables are not used, the following equations will be required to calculate
532:
The blower door fan is temporarily sealed into an exterior doorway using the door panel system. All interior doors are opened, and all exterior doors and windows are closed. HVAC balancing dampers and registers are not to be adjusted, and fireplaces and other operable dampers should be closed. All
4086:
which represents the duration for which the room will retain at least 85% of the design concentration in order to suppress a fire and to ensure it does not reignite. This retention time inversely proportion to the leakage area of the room which is the major factor. Location of leaks, height being
263:
While these blower door-testing efforts were useful in identifying leakage pathways and in accounting for otherwise inexplicable energy losses, the results could not be used to determine real-time air exchange in buildings under natural conditions, or even to determine average annual air exchange
3008:
Often, an effort is made to control for building size and layout by normalizing the airflow at a specified building pressure to either the building's floor area or to its total surface area. These values are generated by taking the airflow rate through the fan and dividing by the area. These
4033:
of forced air heating/cooling systems - both supply (vents) ducts and return ducts can be tested to determine if and how much they leak air. A duct test can be combined with a blower door test to measure the total leakage to outside, measuring effective leakage to the outside of the house
712:
The C parameter reflects the size of the orifice, the โˆ†P is the pressure differential across the orifice, and the n parameter represents the characteristic shape of the orifice, with values ranging from 0.5 to 1, representing a perfect orifice and a very long, thin crack, respectively.
3009:
metrics are most used to assess construction and building envelope quality, because they normalize the total building leakage area to the total amount of area through which that leakage could occur. In other words, how much leakage occurs per unit area of wall, floor, ceiling, etc.
3000:). This standardized single-point test allows for comparison between homes measured at the same reference pressure. This is a raw number reflecting only the flow of air through the fan. Homes of different sizes and similar envelope quality will have different results in this test. 2982:
Depending on how a blower door test is performed, a wide variety of airtightness and building airflow metrics can be derived from the gathered data. Some of the most common metrics and their variations are discussed below. The examples below use the SI pressure measurement unit
181:
A variety of blower door air tightness metrics can be produced using the combination of building-to-outside pressure and fan airflow measurements. These metrics differ in their measurement methods, calculation and uses. Blower door tests are used by building researchers,
4037:
Finding air leaks in a building using an infrared camera while the house is depressurized. A blower door is not mandatory for an infrared reading, but the drawing in of outside air temperatures exaggerates temperature changes and facilitates the spotting of envelope
206:
In Sweden blower door technology was first used to measure building air tightness in 1977. The earliest implementation in Sweden used a fan mounted in a window, rather than a door. By 1979, similar window-mounted measurement techniques were being pursued in
1247: 168:, to simultaneously measure the pressure differential induced across the face of the fan and across the building envelope, as a result of fan airflow; and a mounting system, used to mount the fan in a building opening, such as a door or a window. 2439: 2186: 3388: 253:
used blower doors to identify thermal bypasses. These bypasses were air leakage sites, such as attic utility chases, that accounted for the largest percentage of air leakage energy loss in most homes. Use of blower doors in home energy
4078:
The NFPA standard requires that the blower door operator be trained, but does not specify the nature or source of this training. There is no official NFPA training available for enclosure integrity testing methodology at this time.
985: 2726: 3796: 1924: 1548: 491:(LBNL). This model combined data derived from blower door tests with annual weather data to generate time-resolved ventilation rates for a given home in a specific location. This model has been incorporated into the 4279:
Tamura, G. T. (1975). Measurement of air leakage characteristics of house enclosures. ASHRAE Transactions, 81(1), 202โ€“211. Presented at the 1975 ASHRAE Semiannual Meeting, Atlantic City, NJ, USA, Jan 26–30,
2987:(pa). Imperial measurement units are commonly water column inches (WC Inch or IWC). The conversion rate is 1 WC inch = 249 Pa. Examples below use the commonly accepted pressure of 50pa which is 20% of 1 IWC. 1301:
An alternative approach to the multi-point procedure is to only measure fan airflow and building pressure differential at a single test point, such as 50 Pa, and then use an assumed pressure exponent,
827: 369: 3112: 2995:
This is the first metric that results from a Blower Door Test. The airflow, (Imperial in Cubic Feet / minute; SI in liters / second) at a given building-to-outside pressure differential, 50 pascal
495:
Handbook of Fundamentals (1989), and it has been used in the development of ASHRAE Standards 119 and 136. Other infiltration models have been developed elsewhere, including one by Deru and Burns at the
4289:
Orr, H. W., & Figley, D. A. (1980). An exhaust fan apparatus for assessing the air leakage characteristics of houses. National Research Council of Canada. Building Research Note, no. BRN-156.
260:
The blower door first became commercially available in the United States in 1980 under the name Gadsco. Harmax started to sell units in 1981, followed closely by The Energy Conservatory in 1982.
2030: 1978: 5863: 3649:
The ELA can be used, along with the Specific Infiltration Rate(s) derived using the LBNL infiltration model, to determine airflow rate through the building envelope throughout the year.
3680:
Normalized leakage is a measure of the tightness of a building envelope relative to the building size and number of stories. Normalized leakage is defined in ASHRAE Standard 119 as:
1058: 605: 3536: 482: 4409:
Sherman, Max; D.T. Grimsrud (October 1980). The Measurement of Infiltration using Fan Pressurization and Weather Data (Report). Lawrence Berkeley National Laboratory. LBL-10852.
2896: 1603: 1067: 3592: 3470: 3232: 1655: 1420: 1370: 2963: 2846: 2476: 2316: 1795: 2928: 2772: 2220: 2065: 1758: 682: 3896: 2323: 421: 3149: 3957: 2809: 2611: 2576: 2537: 2076: 1725: 1690: 3180: 2278: 3494: 1284:
values are ยฑ5, 10, 20, 30, 40 and 50 pascal. Ordinary least squares regression analysis is then used to calculate the leakage characteristics of the building envelope:
3853: 3418: 3253: 3823: 3920: 2500: 2244: 706: 653: 629: 4333:
Diamond, R.C.; J.B. Dickinson; R.D. Lipschutz; B. O'Regan; B. Schole (1982). The House Doctor's Manual (Report). Lawrence Berkeley National Laboratory. PUB-3017.
4050:
enclosure integrity testing is a specialized type of enclosure testing that typically measures the airtightness of rooms within buildings that are protected by
5813: 5843: 833: 2618: 4067:
refers to the fact that after the suppression system discharges, there is nothing to be cleaned up; the agent merely disperses into the atmosphere.
3685: 1806: 1430: 4159: 4269:
Harrje, D.T.; A. Blomsterberg; A. Persily (1979). Reduction of Air Infiltration Due to Window and Door Retrofits (Report). CU/CEES. Report 85.
5858: 5351: 4600: 4466:
Deru, M.; P. Burns (2003). "Infiltration and natural ventilation model for whole building energy simulation of residential buildings".
4362: 735: 1322:
corrections should be applied to all airflow data. This must be done prior to the derivation of building air leakage coefficients (
5853: 5785: 269: 264:
levels. Sherman attributes the first attempt at doing this to Persily and Kronvall, who estimated annual average air exchange by:
3026: 520:
A basic blower door system includes three components: a calibrated fan, a door panel system, and a pressure measurement device (
4299:
Harrje, D.T.; G.S. Dutt; J.E. Beya (1979). "Locating and Eliminating Obscure, but Major Energy Losses in Residential Housing".
4007: 5658: 4184: 488: 5818: 5780: 4047: 4020: 497: 230:, as part of a Division of Building Research study to test houses in Ottawa in 1967–1968 and was published in 1975. 93: 4544: 3665:
units of 1.25 square inches (8.1 cm) of leakage area per 100 square feet (9.3 m) of enclosure area, to control
234: 4000: 1983: 1931: 487:
Further physical modeling efforts allowed for the development and validation of an infiltration model by researchers at
65: 5641: 3017:
Another common metric is the air changes per hour at a specified building pressure, again, typically at 50 Pa (ACH
257:
and weatherization efforts became known as "house doctoring" by researchers on the east and west United States coasts.
5683: 5396: 4932: 4661: 112: 4752: 160:, capable of inducing a range of airflows sufficient to pressurize and depressurize a variety of building sizes; a 72: 4054:. This test is normally done during the installation and commissioning of the system and is mandatory under NFPA, 5833: 5647: 5027: 501: 175: 4345: 4591: 4424:. Measured Air Leakage Performance of Buildings. ASTM. pp. 325โ€“347. Special Technical Publication No. 904. 50: 994: 174:
testing is usually thought of in residential settings. It is becoming more common in commercial settings. The
5795: 5739: 5734: 5311: 4839: 79: 5356: 4907: 4828: 4787: 4163: 3657:
Leakage area estimates can also be normalized for the size of the enclosure being tested, For example, the
567: 46: 3501: 1242:{\displaystyle C_{Fan}{{\Delta }P_{Fan}}^{n_{Fan}}=C_{Building}{{\Delta }P_{Building}}^{n_{Building}}\,\!} 428: 5699: 5501: 5012: 4947: 4865: 4777: 4641: 2857: 61: 5848: 5729: 5436: 5201: 5045: 2613:
from the blower door manufacturer to the actual volumetric airflow through the fan, use the following:
1555: 195: 3547: 3425: 3187: 2434:{\displaystyle \rho _{Out}=0.07517*(1-{0.0035666*E \over 528})^{5.2553}*({528 \over T_{Out}+460})\,\!} 1610: 1375: 1325: 5901: 5760: 5724: 5526: 5156: 5111: 5039: 4891: 4834: 2933: 2816: 2446: 2286: 1765: 16:
This article is about the temporary test equipment. For the blower usually mounted above a door, see
2901: 2733: 2193: 2181:{\displaystyle \rho _{In}=0.07517*(1-{0.0035666*E \over 528})^{5.2553}*({528 \over T_{In}+460})\,\!} 2038: 1731: 660: 5948: 5770: 5466: 5066: 4845: 4736: 4721: 4051: 3992:
Blower doors can be used in a variety of types of testing. These include (but are not limited to):
3860: 375: 3119: 5943: 5868: 5790: 5719: 5663: 5595: 5491: 5406: 5316: 5281: 4757: 3927: 2779: 2581: 2546: 2507: 1695: 1660: 216: 39: 3383:{\displaystyle ELA=C_{Building}*{\sqrt {\rho \over 2}}*{\Delta }P_{Ref}^{n_{Building}-0.5}\,\!} 3156: 2251: 5933: 5895: 5775: 5486: 4917: 3477: 5953: 5631: 5590: 5306: 4977: 4797: 4569: 4439:
ASHRAE Standard 119, Air Leakage Performance for Detached Single-Family Residential Buildings
3830: 3662: 3395: 142: 3803: 5974: 5755: 5745: 5689: 5626: 5521: 5101: 5050: 4616: 4360: 4227: 4210: 4138: 4116: 4030: 3903: 2483: 2227: 689: 636: 612: 242: 212: 161: 4562: 137:
is a machine used to perform a building air leakage test. It can also be used to measure
8: 5621: 5611: 5585: 5371: 5033: 4942: 4912: 4812: 4782: 4676: 4636: 1265:
values that are provided by the blower door manufacturer, and they are used to calculate
716:
There are two airflows to be determined in blower door testing, airflow through the fan (
562:
equation of flow through an orifice. The orifice flow equation is typically expressed as
86: 5884: 5828: 5765: 5542: 5421: 5416: 5206: 5017: 5002: 4584: 4506: 4332: 4232: 1422:). The following methods are used to correct blower door data to standard conditions. 5456: 5411: 5166: 5161: 5091: 4987: 4823: 4626: 4510: 4395: 4236: 4017:
Testing building envelopes and window frames for water tightness and rain penetration
1272:. The multi-point blower door test procedure results in a series of known values of Q 146: 4530:
ASTM Standard E779-87, Test Method for Determining Air Leakage by Fan Pressurization
5923: 5678: 5673: 5256: 4962: 4860: 4855: 4850: 4767: 4498: 4453:
ASHRAE Standard 136, A Method of Determining Air Change Rates in Detached Dwellings
4391: 4222: 4101: 4006:
Testing buildings for compliance with standards for energy efficiency, such as the
980:{\displaystyle Q_{Building}=C_{Building}{{\Delta }P_{Building}}^{n_{Building}}\,\!} 187: 4455:. American Society of Heating, Refrigeration and Air Conditioning Engineers. 1993. 4441:. American Society of Heating, Refrigeration and Air Conditioning Engineers. 1988. 4188: 152:
There are three primary components to a blower door: a calibrated, variable-speed
5918: 5890: 5532: 5446: 5441: 5386: 5376: 5366: 5296: 5236: 5151: 5136: 4957: 4952: 4927: 4922: 4792: 4716: 4366: 2721:{\displaystyle Q_{Actual}=Q_{Fan}*{\sqrt {\rho _{Ref} \over \rho _{Actual}}}\,\!} 512: 153: 4082:
An NFPA enclosure integrity test result is typically reported in the form of an
550: 125: 5668: 5565: 5341: 5321: 5286: 5221: 5141: 4982: 4972: 4881: 4731: 4701: 4656: 4651: 4111: 4106: 3635: 2068: 227: 183: 4023:
Clean Agent Retention testing (this type of testing is usually described as a
5968: 5750: 5601: 5496: 5461: 5231: 5226: 5181: 5176: 5022: 4997: 4992: 4967: 4937: 4807: 4706: 4686: 4666: 4577: 3791:{\displaystyle NL=1000*({ELA \over A_{Floor}})*({H \over H_{Ref}})^{0.3}\,\!} 2984: 2811:= Volumetric airflow calculated using manufacturer's coefficients or software 1919:{\displaystyle Q_{Corrected}=Q_{Measured}*{\rho _{Out} \over \rho _{In}}\,\!} 1543:{\displaystyle Q_{Corrected}=Q_{Measured}*{\rho _{In} \over \rho _{Out}}\,\!} 246: 157: 4486: 4379: 989:
It is assumed in blower door analysis that mass is conserved, resulting in:
5928: 5606: 5506: 5481: 5476: 5471: 5401: 5336: 5216: 5186: 5126: 5121: 5096: 5007: 4886: 4802: 4726: 4711: 4696: 4096: 254: 191: 171: 3598:
It is essential that units are carefully conserved in these calculations.
5938: 5537: 5511: 5451: 5431: 5426: 5301: 5261: 5246: 5191: 5116: 5086: 5081: 4897: 4762: 4681: 4059: 2849: 1319: 4546:
Minneapolis Blower Door Operation Manual for Model 3 and Model 4 Systems
3976: 3012: 5694: 5616: 5547: 5516: 5391: 5361: 5291: 5241: 5211: 5196: 5171: 5076: 4876: 4772: 4691: 4631: 238: 4502: 3984: 5653: 5331: 5326: 5276: 5251: 5106: 4902: 4268: 4160:"Unmasking Commercial Building Energy Loss | RSES Journal March 2014" 1425:
For depressurization testing, the following equation should be used:
559: 521: 165: 28: 5636: 5570: 5071: 4871: 4671: 4646: 4621: 3496:= Air density (kg/m or lb/in), typically a standard density is used 2974: 1801:
For pressurization testing, the following equation should be used:
516:
Blower door setup in doorway with a digital pressure and flow gauge
17: 3661:
Green Building Rating System has set an airtightness standard for
5146: 4818: 3666: 138: 4380:"Estimation of infiltration from leakage and climate indicators" 3980:
Infrared view of leaky window pressurized by blower door testing
5823: 5575: 5381: 5131: 4011: 1318:
In order to increase the accuracy of blower door test results,
822:{\displaystyle Q_{Fan}=C_{Fan}{{\Delta }P_{Fan}}^{n_{Fan}}\,\!} 492: 211:, and door-mounted test fans were being developed by a team at 178:(GSA) requires testing of new US federal government buildings. 4599: 3996:
Testing residential and commercial buildings for air tightness
3652: 3003: 222:
In Canada the initial concept similarly involved the use of a
198:
and to assess compliance with building performance standards.
5838: 5271: 3960: 3669: 364:{\displaystyle ACH_{natural}={ACH_{at50pascal} \over 20}\,\!} 208: 2318:
can be calculated in IP units using the following equation:
5346: 5266: 3964: 3658: 3107:{\displaystyle ACH_{50}={Q_{50}*60 \over V_{Building}}\,\!} 2990: 4532:. American Society of Testing and Materials (ASTM). 1991. 4408: 4055: 4524: 4522: 4520: 4487:"A Power Law Formulation of Laminar Flow in Short Pipes" 4298: 3620:
should be kg/m and pascal, respectively. Alternatively,
3542:/in), typically 4 Pa in US and 10 Pa in Canada 4542: 4419: 3613: 2543:
In order to translate the airflow values derived using
554:
A typical graph of air leakage vs. pressure (in French)
145:
and to help physically locate air leakage sites in the
4563:
http://www.us.sbt.siemens.com/siemensleed/EAC9C15D.htm
4433: 4431: 4320:
House Doctors Program: Retrofits in Existing Buildings
4517: 4317: 4250:
Caffey, G.E. (1979). "Residential Air Infiltration".
3930: 3906: 3863: 3833: 3806: 3688: 3550: 3504: 3480: 3428: 3398: 3256: 3190: 3159: 3122: 3029: 3013:
Air changes per hour at a specified building pressure
2936: 2904: 2860: 2819: 2782: 2736: 2621: 2584: 2549: 2510: 2486: 2449: 2326: 2289: 2254: 2230: 2196: 2079: 2041: 1986: 1934: 1809: 1768: 1734: 1698: 1663: 1613: 1558: 1433: 1378: 1328: 1070: 997: 836: 738: 692: 663: 639: 615: 570: 431: 378: 272: 4428: 4042: 3182:= Airflow at 50 pascal (ft/minute or m/minute) 226:, which was first utilized by G. T. Tamura in 53:. Unsourced material may be challenged and removed. 3951: 3914: 3890: 3847: 3817: 3790: 3672:between units. This is equal to 0.868 cm/m. 3586: 3530: 3488: 3464: 3412: 3382: 3226: 3174: 3143: 3106: 2957: 2922: 2890: 2852:(typically 1.204 for kg/m or 0.075 for lb/ft) 2840: 2803: 2766: 2720: 2605: 2570: 2531: 2494: 2478:= Air density outside the building, during testing 2470: 2433: 2310: 2272: 2238: 2214: 2180: 2059: 2025:{\displaystyle {\rho _{In} \over \rho _{Out}}\,\!} 2024: 1973:{\displaystyle {\rho _{Out} \over \rho _{In}}\,\!} 1972: 1918: 1797:= Air density outside the building, during testing 1789: 1752: 1719: 1684: 1649: 1597: 1542: 1414: 1364: 1241: 1052: 979: 821: 700: 676: 647: 623: 599: 476: 415: 363: 215:to help them find and fix air leaks in homes in a 4187:. Everydaygreendc.com. 2012-11-30. Archived from 3948: 3911: 3887: 3844: 3814: 3787: 3583: 3527: 3485: 3461: 3409: 3379: 3223: 3171: 3140: 3103: 2954: 2919: 2887: 2837: 2800: 2763: 2717: 2602: 2567: 2528: 2491: 2467: 2430: 2307: 2269: 2235: 2222:= Air density inside the building, during testing 2211: 2177: 2056: 2021: 1969: 1915: 1786: 1760:= Air density inside the building, during testing 1749: 1716: 1681: 1646: 1594: 1539: 1411: 1361: 1238: 1049: 976: 818: 697: 673: 644: 620: 596: 473: 360: 5966: 4139:"Blower Door Tests | Department of Energy" 2898:= Actual density of air going through the fan 4585: 4422:Infiltration Using the LBL Infiltration Model 723:) and airflow through the building envelope ( 545: 507: 4465: 3151:= Air changes per hour at 50 pascal (h) 4552:. Minneapolis, MN: The Energy Conservatory. 4343: 3653:Leakage area per unit floor or surface area 3004:Airflow per unit surface area or floor area 2774:= Actual volumetric airflow through the fan 5352:High efficiency glandless circulating pump 4601:Heating, ventilation, and air conditioning 4592: 4578: 1313: 484:= Air Changes per Hour at 50 pascal 4226: 3999:Testing buildings at mid-construction to 3947: 3910: 3886: 3843: 3813: 3786: 3582: 3526: 3484: 3460: 3408: 3378: 3242: 3239:in determinations of indoor air quality. 3222: 3170: 3139: 3102: 2953: 2918: 2886: 2836: 2799: 2762: 2716: 2601: 2566: 2527: 2490: 2466: 2429: 2306: 2268: 2234: 2210: 2176: 2055: 2020: 1968: 1914: 1785: 1748: 1715: 1680: 1645: 1605:= Airflow corrected to actual air density 1593: 1538: 1410: 1360: 1237: 1048: 975: 817: 696: 672: 643: 619: 595: 472: 359: 113:Learn how and when to remove this message 5786:Mold growth, assessment, and remediation 3983: 3975: 2991:Airflow at a specified building pressure 2973: 1053:{\displaystyle Q_{Fan}=Q_{Building}\,\!} 549: 511: 124: 4484: 4377: 4208: 3988:Visible light view of window under test 5967: 4344:Corporation, Bonnier (November 1981). 4322:. 2nd AIVC Conference. pp. 61โ€“72. 4249: 4228:10.1111/j.1600-0668.1995.t01-1-00008.x 2969: 5659:Programmable communicating thermostat 4573: 3675: 1310:fan calibration and to wind effects. 600:{\displaystyle Q=C{\Delta }P^{n}\,\!} 489:Lawrence Berkeley National Laboratory 5781:Mechanical, electrical, and plumbing 4052:clean agent fire suppression systems 3531:{\displaystyle {\Delta }P_{Ref}\,\!} 498:National Renewable Energy Laboratory 477:{\displaystyle ACH_{at50pascal}\,\!} 51:adding citations to reliable sources 22: 558:Building leakage is described by a 235:National Research Council of Canada 13: 5642:Minimum efficiency reporting value 4420:Sherman, Max; M.P. Modera (1984). 3855:= Effective Leakage Area (m or in) 3506: 3472:= Building air leakage coefficient 3420:= Effective Leakage Area (m or in) 3319: 2891:{\displaystyle \rho _{Actual}\,\!} 1167: 1090: 905: 777: 665: 581: 14: 5986: 5684:Standard temperature and pressure 5397:Packaged terminal air conditioner 4933:Passive daytime radiative cooling 4662:Heat pump and refrigeration cycle 4209:Sherman, Max (1 September 1995). 4001:identify and correct any failures 2978:Blower door installation (France) 1598:{\displaystyle Q_{Corrected}\,\!} 536: 4753:Absorption-compression heat pump 4543:The Energy Conservatory (2010). 4378:Sherman, Max (1 February 1987). 4318:Harrje, D.T.; G.S. Dutt (1981). 4043:NFPA enclosure integrity testing 3587:{\displaystyle n_{Building}\,\!} 3465:{\displaystyle C_{Building}\,\!} 3227:{\displaystyle V_{Building}\,\!} 2502:= Elevation above sea level (ft) 2246:= Elevation above sea level (ft) 1650:{\displaystyle Q_{Measured}\,\!} 1415:{\displaystyle n_{Building}\,\!} 1365:{\displaystyle C_{Building}\,\!} 1251:Fan airflow is determined using 423:= Natural Air Changes per Hour 141:between building zones, to test 27: 5648:Normal temperature and pressure 5028:Vapor-compression refrigeration 4556: 4536: 4478: 4459: 4445: 4413: 4402: 4371: 4354: 4337: 4326: 4311: 4121:Blower Doors In Popular Culture 4027:rather than a blower door test) 3971: 3898:= Building floor area (m or in) 2958:{\displaystyle \rho _{Out}\,\!} 2841:{\displaystyle \rho _{Ref}\,\!} 2471:{\displaystyle \rho _{Out}\,\!} 2311:{\displaystyle \rho _{Out}\,\!} 1790:{\displaystyle \rho _{Out}\,\!} 502:building performance simulation 176:General Services Administration 38:needs additional citations for 4292: 4283: 4273: 4262: 4243: 4211:"The Use of Blower-Door Data1" 4202: 4177: 4152: 4131: 3777: 3750: 3744: 3704: 3538:= Reference pressure (Pa or lb 2923:{\displaystyle \rho _{In}\,\!} 2767:{\displaystyle Q_{Actual}\,\!} 2426: 2392: 2380: 2352: 2215:{\displaystyle \rho _{In}\,\!} 2173: 2142: 2130: 2102: 2071:using the following equation: 2060:{\displaystyle \rho _{In}\,\!} 1753:{\displaystyle \rho _{In}\,\!} 677:{\displaystyle {\Delta }P\,\!} 1: 5796:Testing, adjusting, balancing 5740:Building information modeling 5735:Building services engineering 5312:Ground-coupled heat exchanger 4840:Demand controlled ventilation 4788:Building insulation materials 4491:Journal of Fluids Engineering 4185:"What is a Blower Door Test?" 4125: 3891:{\displaystyle A_{Floor}\,\!} 527: 416:{\displaystyle ACH_{natural}} 129:Single fan blower door system 5357:High-pressure cut-off switch 4908:Ice storage air conditioning 4829:Dedicated outdoor air system 4396:10.1016/0378-7788(87)90008-9 4063:sprinkler system. The word 3594:= Building pressure exponent 3144:{\displaystyle ACH_{50}\,\!} 684:= Pressure differential (Pa) 7: 5700:Thermostatic radiator valve 5502:Thermostatic radiator valve 5013:Underfloor air distribution 4948:Radiant heating and cooling 4866:Energy recovery ventilation 4778:Automobile air conditioning 4642:Domestic energy consumption 4090: 3952:{\displaystyle H_{Ref}\,\!} 3922:= Building height (m or in) 3612:should be calculated using 3234:= Building volume (ft or m) 2804:{\displaystyle Q_{Fan}\,\!} 2606:{\displaystyle n_{Fan}\,\!} 2571:{\displaystyle C_{Fan}\,\!} 2532:{\displaystyle T_{Out}\,\!} 1720:{\displaystyle n_{Fan}\,\!} 1685:{\displaystyle C_{Fan}\,\!} 10: 5991: 5849:Institute of Refrigeration 5730:Architectural technologist 5202:Electrostatic precipitator 4365:November 11, 2014, at the 4075:is generally ten minutes. 3175:{\displaystyle Q_{50}\,\!} 2273:{\displaystyle T_{In}\,\!} 1372:) and pressure exponents ( 546:Power law model of airflow 508:How blower door tests work 201: 15: 5911: 5902:Volatile organic compound 5877: 5804: 5761:Environmental engineering 5725:Architectural engineering 5708: 5556: 5527:Ultra-low particulate air 5112:Automatic balancing valve 5059: 5040:Variable refrigerant flow 4892:Heat recovery ventilation 4835:Deep water source cooling 4745: 4607: 3489:{\displaystyle \rho \,\!} 2930:for depressurization and 2539:= Outdoor temperature (F) 655:= Air leakage coefficient 500:(NREL), for use in whole- 233:In Canada, a team at the 5949:Template:Home automation 5771:Kitchen exhaust cleaning 5467:Solar-assisted heat pump 5067:Air conditioner inverter 4846:Displacement ventilation 4737:Vapour pressure of water 4722:Thermal destratification 4141:. Energy.gov. 2012-04-02 3959:= Reference height (2.5 3634:can be calculated using 2280:= Indoor temperature (F) 1657:= Airflow derived using 5944:World Refrigeration Day 5791:Refrigerant reclamation 5720:Architectural acoustics 5664:Programmable thermostat 5596:Clean air delivery rate 5492:Thermal expansion valve 5407:Pressurisation ductwork 5317:Ground source heat pump 4758:Absorption refrigerator 3848:{\displaystyle ELA\,\!} 3413:{\displaystyle ELA\,\!} 1314:Air density corrections 217:Twin Rivers, New Jersey 5934:Glossary of HVAC terms 5896:Sick building syndrome 5776:Mechanical engineering 5487:Smoke exhaust ductwork 4918:Mixed-mode ventilation 4350:. Bonnier Corporation. 3989: 3981: 3953: 3916: 3892: 3849: 3819: 3818:{\displaystyle NL\,\!} 3792: 3588: 3532: 3490: 3466: 3414: 3384: 3243:Effective leakage area 3228: 3176: 3145: 3108: 2979: 2959: 2924: 2892: 2842: 2805: 2768: 2722: 2607: 2572: 2533: 2496: 2472: 2435: 2312: 2274: 2240: 2216: 2182: 2061: 2026: 1974: 1920: 1791: 1754: 1721: 1686: 1651: 1599: 1544: 1416: 1366: 1243: 1054: 981: 823: 702: 678: 649: 625: 601: 555: 517: 478: 417: 365: 130: 5954:Template:Solar energy 5632:Intelligent buildings 5591:Carbon dioxide sensor 4978:Room air distribution 4798:Central solar heating 4485:Sherman, Max (1992). 3987: 3979: 3954: 3917: 3915:{\displaystyle H\,\!} 3893: 3850: 3820: 3793: 3663:multi-family dwelling 3589: 3533: 3491: 3467: 3415: 3385: 3229: 3177: 3146: 3109: 2977: 2960: 2925: 2893: 2843: 2806: 2769: 2723: 2608: 2573: 2534: 2497: 2495:{\displaystyle E\,\!} 2473: 2436: 2313: 2275: 2241: 2239:{\displaystyle E\,\!} 2217: 2183: 2067:can be calculated in 2062: 2027: 1975: 1921: 1792: 1755: 1722: 1687: 1652: 1600: 1545: 1417: 1367: 1244: 1055: 982: 824: 703: 701:{\displaystyle n\,\!} 679: 650: 648:{\displaystyle C\,\!} 626: 624:{\displaystyle Q\,\!} 602: 553: 515: 479: 418: 366: 219:housing development. 164:instrument, called a 143:ductwork airtightness 128: 5756:Duct leakage testing 5746:Deep energy retrofit 5690:Thermographic camera 5627:Infrared thermometer 5102:Air source heat pump 5051:Water heat recycling 4617:Air changes per hour 4384:Energy and Buildings 4117:Efficient energy use 4031:Duct leakage testing 3928: 3904: 3861: 3831: 3825:= Normalized leakage 3804: 3686: 3548: 3502: 3478: 3426: 3396: 3254: 3188: 3157: 3120: 3027: 2934: 2902: 2858: 2817: 2780: 2734: 2619: 2582: 2547: 2508: 2484: 2447: 2324: 2287: 2252: 2228: 2194: 2077: 2039: 1984: 1932: 1807: 1766: 1732: 1696: 1661: 1611: 1556: 1431: 1376: 1326: 1068: 995: 834: 736: 690: 661: 637: 613: 568: 429: 376: 270: 213:Princeton University 162:pressure measurement 47:improve this article 5622:HVAC control system 5612:Home energy monitor 5586:Building automation 5372:Inverter compressor 5034:Variable air volume 4943:Passive ventilation 4913:Kitchen ventilation 4813:Constant air volume 4783:Autonomous building 4468:ASHRAE Transactions 4301:ASHRAE Transactions 4252:ASHRAE Transactions 3646:/in, respectively. 3616:units, and ฯ and โˆ†P 3377: 2970:Blower door metrics 708:= Pressure exponent 5885:Indoor air quality 5829:ASTM International 5766:Hydronic balancing 5543:Wood-burning stove 5422:Radiator reflector 5207:Evaporative cooler 5018:Underfloor heating 5003:Thermal insulation 3990: 3982: 3949: 3912: 3888: 3845: 3815: 3788: 3676:Normalized leakage 3642:being lb/ft and lb 3584: 3528: 3486: 3462: 3410: 3380: 3323: 3224: 3172: 3141: 3104: 2980: 2965:for pressurization 2955: 2920: 2888: 2838: 2801: 2764: 2718: 2603: 2568: 2529: 2492: 2468: 2431: 2308: 2270: 2236: 2212: 2178: 2057: 2022: 1970: 1916: 1787: 1750: 1717: 1682: 1647: 1595: 1540: 1412: 1362: 1239: 1062:Which results in: 1050: 977: 819: 698: 674: 645: 621: 597: 556: 518: 474: 413: 361: 190:contractors, home 131: 5962: 5961: 5878:Health and safety 5457:Scroll compressor 5412:Process duct work 5167:Convection heater 5162:Condensing boiler 5092:Air-mixing plenum 4988:Solar combisystem 4824:Cross ventilation 4627:Building envelope 4503:10.1115/1.2910073 3774: 3742: 3313: 3312: 3100: 2714: 2713: 2424: 2377: 2171: 2127: 2018: 1966: 1912: 1536: 357: 147:building envelope 123: 122: 115: 97: 5982: 5924:Building science 5679:Smart thermostat 5674:Room temperature 5257:Fireplace insert 4963:Radon mitigation 4861:Electric heating 4856:District heating 4851:District cooling 4768:Air conditioning 4594: 4587: 4580: 4571: 4570: 4565: 4560: 4554: 4553: 4551: 4540: 4534: 4533: 4526: 4515: 4514: 4482: 4476: 4475: 4463: 4457: 4456: 4449: 4443: 4442: 4435: 4426: 4425: 4417: 4411: 4410: 4406: 4400: 4399: 4375: 4369: 4358: 4352: 4351: 4341: 4335: 4334: 4330: 4324: 4323: 4315: 4309: 4308: 4296: 4290: 4287: 4281: 4277: 4271: 4270: 4266: 4260: 4259: 4247: 4241: 4240: 4230: 4206: 4200: 4199: 4197: 4196: 4181: 4175: 4174: 4172: 4171: 4162:. Archived from 4156: 4150: 4149: 4147: 4146: 4135: 4102:Home performance 4003:in the enclosure 3958: 3956: 3955: 3950: 3946: 3945: 3921: 3919: 3918: 3913: 3897: 3895: 3894: 3889: 3885: 3884: 3854: 3852: 3851: 3846: 3824: 3822: 3821: 3816: 3797: 3795: 3794: 3789: 3785: 3784: 3775: 3773: 3772: 3754: 3743: 3741: 3740: 3719: 3708: 3633: 3626: 3611: 3604: 3593: 3591: 3590: 3585: 3581: 3580: 3537: 3535: 3534: 3529: 3525: 3524: 3509: 3495: 3493: 3492: 3487: 3471: 3469: 3468: 3463: 3459: 3458: 3419: 3417: 3416: 3411: 3389: 3387: 3386: 3381: 3376: 3369: 3368: 3337: 3322: 3314: 3305: 3304: 3299: 3298: 3233: 3231: 3230: 3225: 3221: 3220: 3181: 3179: 3178: 3173: 3169: 3168: 3150: 3148: 3147: 3142: 3138: 3137: 3113: 3111: 3110: 3105: 3101: 3099: 3098: 3068: 3061: 3060: 3050: 3045: 3044: 2964: 2962: 2961: 2956: 2952: 2951: 2929: 2927: 2926: 2921: 2917: 2916: 2897: 2895: 2894: 2889: 2885: 2884: 2847: 2845: 2844: 2839: 2835: 2834: 2810: 2808: 2807: 2802: 2798: 2797: 2773: 2771: 2770: 2765: 2761: 2760: 2727: 2725: 2724: 2719: 2715: 2712: 2711: 2687: 2686: 2671: 2670: 2665: 2664: 2646: 2645: 2612: 2610: 2609: 2604: 2600: 2599: 2577: 2575: 2574: 2569: 2565: 2564: 2538: 2536: 2535: 2530: 2526: 2525: 2501: 2499: 2498: 2493: 2477: 2475: 2474: 2469: 2465: 2464: 2440: 2438: 2437: 2432: 2425: 2423: 2416: 2415: 2396: 2388: 2387: 2378: 2373: 2362: 2342: 2341: 2317: 2315: 2314: 2309: 2305: 2304: 2279: 2277: 2276: 2271: 2267: 2266: 2245: 2243: 2242: 2237: 2221: 2219: 2218: 2213: 2209: 2208: 2187: 2185: 2184: 2179: 2172: 2170: 2163: 2162: 2146: 2138: 2137: 2128: 2123: 2112: 2092: 2091: 2066: 2064: 2063: 2058: 2054: 2053: 2031: 2029: 2028: 2023: 2019: 2017: 2016: 2001: 2000: 1988: 1979: 1977: 1976: 1971: 1967: 1965: 1964: 1952: 1951: 1936: 1925: 1923: 1922: 1917: 1913: 1911: 1910: 1898: 1897: 1882: 1877: 1876: 1843: 1842: 1796: 1794: 1793: 1788: 1784: 1783: 1759: 1757: 1756: 1751: 1747: 1746: 1726: 1724: 1723: 1718: 1714: 1713: 1691: 1689: 1688: 1683: 1679: 1678: 1656: 1654: 1653: 1648: 1644: 1643: 1604: 1602: 1601: 1596: 1592: 1591: 1549: 1547: 1546: 1541: 1537: 1535: 1534: 1519: 1518: 1506: 1501: 1500: 1467: 1466: 1421: 1419: 1418: 1413: 1409: 1408: 1371: 1369: 1368: 1363: 1359: 1358: 1308: 1297: 1290: 1271: 1264: 1257: 1248: 1246: 1245: 1240: 1236: 1235: 1234: 1233: 1202: 1201: 1200: 1170: 1163: 1162: 1129: 1128: 1127: 1126: 1110: 1109: 1108: 1093: 1086: 1085: 1059: 1057: 1056: 1051: 1047: 1046: 1013: 1012: 986: 984: 983: 978: 974: 973: 972: 971: 940: 939: 938: 908: 901: 900: 867: 866: 828: 826: 825: 820: 816: 815: 814: 813: 797: 796: 795: 780: 773: 772: 754: 753: 729: 722: 707: 705: 704: 699: 683: 681: 680: 675: 668: 654: 652: 651: 646: 630: 628: 627: 622: 606: 604: 603: 598: 594: 593: 584: 483: 481: 480: 475: 471: 470: 422: 420: 419: 414: 412: 411: 370: 368: 367: 362: 358: 353: 352: 351: 311: 306: 305: 188:home performance 118: 111: 107: 104: 98: 96: 55: 31: 23: 5990: 5989: 5985: 5984: 5983: 5981: 5980: 5979: 5965: 5964: 5963: 5958: 5919:ASHRAE Handbook 5907: 5891:Passive smoking 5873: 5806: 5800: 5712: 5710: 5704: 5558: 5552: 5533:Whole-house fan 5447:Run-around coil 5442:Reversing valve 5387:Mechanical room 5377:Kerosene heater 5367:Infrared heater 5297:Gasoline heater 5237:Fan filter unit 5152:Condensate pump 5137:Centrifugal fan 5055: 4958:Radiant heating 4953:Radiant cooling 4928:Passive cooling 4923:Microgeneration 4793:Central heating 4741: 4717:Thermal comfort 4609: 4603: 4598: 4568: 4561: 4557: 4549: 4541: 4537: 4528: 4527: 4518: 4483: 4479: 4464: 4460: 4451: 4450: 4446: 4437: 4436: 4429: 4418: 4414: 4407: 4403: 4376: 4372: 4367:Wayback Machine 4359: 4355: 4347:Popular Science 4342: 4338: 4331: 4327: 4316: 4312: 4297: 4293: 4288: 4284: 4278: 4274: 4267: 4263: 4248: 4244: 4207: 4203: 4194: 4192: 4183: 4182: 4178: 4169: 4167: 4158: 4157: 4153: 4144: 4142: 4137: 4136: 4132: 4128: 4093: 4084:agent hold time 4045: 3974: 3935: 3931: 3929: 3926: 3925: 3905: 3902: 3901: 3868: 3864: 3862: 3859: 3858: 3832: 3829: 3828: 3805: 3802: 3801: 3780: 3776: 3762: 3758: 3753: 3724: 3720: 3709: 3707: 3687: 3684: 3683: 3678: 3655: 3645: 3641: 3638:, with ฯ and โˆ†P 3632: 3628: 3625: 3621: 3619: 3610: 3606: 3603: 3599: 3555: 3551: 3549: 3546: 3545: 3541: 3514: 3510: 3505: 3503: 3500: 3499: 3479: 3476: 3475: 3433: 3429: 3427: 3424: 3423: 3397: 3394: 3393: 3343: 3339: 3338: 3327: 3318: 3303: 3273: 3269: 3255: 3252: 3251: 3245: 3195: 3191: 3189: 3186: 3185: 3164: 3160: 3158: 3155: 3154: 3133: 3129: 3121: 3118: 3117: 3073: 3069: 3056: 3052: 3051: 3049: 3040: 3036: 3028: 3025: 3024: 3020: 3015: 3006: 2999: 2993: 2972: 2941: 2937: 2935: 2932: 2931: 2909: 2905: 2903: 2900: 2899: 2865: 2861: 2859: 2856: 2855: 2824: 2820: 2818: 2815: 2814: 2787: 2783: 2781: 2778: 2777: 2741: 2737: 2735: 2732: 2731: 2692: 2688: 2676: 2672: 2669: 2654: 2650: 2626: 2622: 2620: 2617: 2616: 2589: 2585: 2583: 2580: 2579: 2554: 2550: 2548: 2545: 2544: 2515: 2511: 2509: 2506: 2505: 2485: 2482: 2481: 2454: 2450: 2448: 2445: 2444: 2405: 2401: 2400: 2395: 2383: 2379: 2363: 2361: 2331: 2327: 2325: 2322: 2321: 2294: 2290: 2288: 2285: 2284: 2259: 2255: 2253: 2250: 2249: 2229: 2226: 2225: 2201: 2197: 2195: 2192: 2191: 2155: 2151: 2150: 2145: 2133: 2129: 2113: 2111: 2084: 2080: 2078: 2075: 2074: 2046: 2042: 2040: 2037: 2036: 2033:air densities. 2006: 2002: 1993: 1989: 1987: 1985: 1982: 1981: 1957: 1953: 1941: 1937: 1935: 1933: 1930: 1929: 1903: 1899: 1887: 1883: 1881: 1851: 1847: 1814: 1810: 1808: 1805: 1804: 1773: 1769: 1767: 1764: 1763: 1739: 1735: 1733: 1730: 1729: 1703: 1699: 1697: 1694: 1693: 1668: 1664: 1662: 1659: 1658: 1618: 1614: 1612: 1609: 1608: 1563: 1559: 1557: 1554: 1553: 1524: 1520: 1511: 1507: 1505: 1475: 1471: 1438: 1434: 1432: 1429: 1428: 1383: 1379: 1377: 1374: 1373: 1333: 1329: 1327: 1324: 1323: 1316: 1307: 1303: 1296: 1292: 1289: 1285: 1283: 1279: 1275: 1270: 1266: 1263: 1259: 1256: 1252: 1208: 1204: 1203: 1175: 1171: 1166: 1165: 1164: 1137: 1133: 1116: 1112: 1111: 1098: 1094: 1089: 1088: 1087: 1075: 1071: 1069: 1066: 1065: 1021: 1017: 1002: 998: 996: 993: 992: 946: 942: 941: 913: 909: 904: 903: 902: 875: 871: 841: 837: 835: 832: 831: 803: 799: 798: 785: 781: 776: 775: 774: 762: 758: 743: 739: 737: 734: 733: 728: 724: 721: 717: 691: 688: 687: 664: 662: 659: 658: 638: 635: 634: 614: 611: 610: 589: 585: 580: 569: 566: 565: 548: 539: 530: 510: 442: 438: 430: 427: 426: 389: 385: 377: 374: 373: 323: 319: 312: 310: 283: 279: 271: 268: 267: 204: 192:energy auditors 119: 108: 102: 99: 56: 54: 44: 32: 21: 12: 11: 5: 5988: 5978: 5977: 5960: 5959: 5957: 5956: 5951: 5946: 5941: 5936: 5931: 5926: 5921: 5915: 5913: 5909: 5908: 5906: 5905: 5899: 5893: 5888: 5881: 5879: 5875: 5874: 5872: 5871: 5866: 5861: 5856: 5851: 5846: 5841: 5836: 5831: 5826: 5821: 5816: 5810: 5808: 5802: 5801: 5799: 5798: 5793: 5788: 5783: 5778: 5773: 5768: 5763: 5758: 5753: 5748: 5743: 5737: 5732: 5727: 5722: 5716: 5714: 5706: 5705: 5703: 5702: 5697: 5692: 5687: 5681: 5676: 5671: 5669:Psychrometrics 5666: 5661: 5656: 5651: 5645: 5639: 5634: 5629: 5624: 5619: 5614: 5609: 5604: 5599: 5593: 5588: 5583: 5578: 5573: 5568: 5566:Air flow meter 5562: 5560: 5554: 5553: 5551: 5550: 5545: 5540: 5535: 5530: 5524: 5519: 5514: 5509: 5504: 5499: 5494: 5489: 5484: 5479: 5474: 5469: 5464: 5459: 5454: 5449: 5444: 5439: 5434: 5429: 5424: 5419: 5414: 5409: 5404: 5399: 5394: 5389: 5384: 5379: 5374: 5369: 5364: 5359: 5354: 5349: 5344: 5342:Heating system 5339: 5334: 5329: 5324: 5322:Heat exchanger 5319: 5314: 5309: 5304: 5299: 5294: 5289: 5287:Gas compressor 5284: 5279: 5274: 5269: 5264: 5259: 5254: 5249: 5244: 5239: 5234: 5229: 5224: 5222:Expansion tank 5219: 5214: 5209: 5204: 5199: 5194: 5189: 5184: 5179: 5174: 5169: 5164: 5159: 5154: 5149: 5144: 5142:Ceramic heater 5139: 5134: 5129: 5124: 5119: 5114: 5109: 5104: 5099: 5094: 5089: 5084: 5079: 5074: 5069: 5063: 5061: 5057: 5056: 5054: 5053: 5048: 5043: 5037: 5031: 5025: 5020: 5015: 5010: 5005: 5000: 4995: 4990: 4985: 4983:Solar air heat 4980: 4975: 4973:Renewable heat 4970: 4965: 4960: 4955: 4950: 4945: 4940: 4935: 4930: 4925: 4920: 4915: 4910: 4905: 4900: 4895: 4889: 4884: 4882:Forced-air gas 4879: 4874: 4869: 4863: 4858: 4853: 4848: 4843: 4837: 4832: 4826: 4821: 4816: 4810: 4805: 4800: 4795: 4790: 4785: 4780: 4775: 4770: 4765: 4760: 4755: 4749: 4747: 4743: 4742: 4740: 4739: 4734: 4732:Thermodynamics 4729: 4724: 4719: 4714: 4709: 4704: 4702:Psychrometrics 4699: 4694: 4689: 4684: 4679: 4674: 4669: 4664: 4659: 4657:Gas compressor 4654: 4652:Fluid dynamics 4649: 4644: 4639: 4634: 4629: 4624: 4619: 4613: 4611: 4605: 4604: 4597: 4596: 4589: 4582: 4574: 4567: 4566: 4555: 4535: 4516: 4497:(4): 601โ€“605. 4477: 4458: 4444: 4427: 4412: 4401: 4370: 4353: 4336: 4325: 4310: 4291: 4282: 4272: 4261: 4242: 4221:(3): 215โ€“224. 4201: 4176: 4151: 4129: 4127: 4124: 4123: 4122: 4119: 4114: 4112:Weatherization 4109: 4107:Green retrofit 4104: 4099: 4092: 4089: 4071:very similar. 4044: 4041: 4040: 4039: 4035: 4028: 4018: 4015: 4004: 3997: 3973: 3970: 3969: 3968: 3944: 3941: 3938: 3934: 3923: 3909: 3899: 3883: 3880: 3877: 3874: 3871: 3867: 3856: 3842: 3839: 3836: 3826: 3812: 3809: 3783: 3779: 3771: 3768: 3765: 3761: 3757: 3752: 3749: 3746: 3739: 3736: 3733: 3730: 3727: 3723: 3718: 3715: 3712: 3706: 3703: 3700: 3697: 3694: 3691: 3677: 3674: 3654: 3651: 3643: 3639: 3636:Imperial units 3630: 3623: 3617: 3608: 3601: 3596: 3595: 3579: 3576: 3573: 3570: 3567: 3564: 3561: 3558: 3554: 3543: 3539: 3523: 3520: 3517: 3513: 3508: 3497: 3483: 3473: 3457: 3454: 3451: 3448: 3445: 3442: 3439: 3436: 3432: 3421: 3407: 3404: 3401: 3375: 3372: 3367: 3364: 3361: 3358: 3355: 3352: 3349: 3346: 3342: 3336: 3333: 3330: 3326: 3321: 3317: 3311: 3308: 3302: 3297: 3294: 3291: 3288: 3285: 3282: 3279: 3276: 3272: 3268: 3265: 3262: 3259: 3244: 3241: 3236: 3235: 3219: 3216: 3213: 3210: 3207: 3204: 3201: 3198: 3194: 3183: 3167: 3163: 3152: 3136: 3132: 3128: 3125: 3097: 3094: 3091: 3088: 3085: 3082: 3079: 3076: 3072: 3067: 3064: 3059: 3055: 3048: 3043: 3039: 3035: 3032: 3018: 3014: 3011: 3005: 3002: 2997: 2992: 2989: 2971: 2968: 2967: 2966: 2950: 2947: 2944: 2940: 2915: 2912: 2908: 2883: 2880: 2877: 2874: 2871: 2868: 2864: 2853: 2833: 2830: 2827: 2823: 2812: 2796: 2793: 2790: 2786: 2775: 2759: 2756: 2753: 2750: 2747: 2744: 2740: 2710: 2707: 2704: 2701: 2698: 2695: 2691: 2685: 2682: 2679: 2675: 2668: 2663: 2660: 2657: 2653: 2649: 2644: 2641: 2638: 2635: 2632: 2629: 2625: 2598: 2595: 2592: 2588: 2563: 2560: 2557: 2553: 2541: 2540: 2524: 2521: 2518: 2514: 2503: 2489: 2479: 2463: 2460: 2457: 2453: 2428: 2422: 2419: 2414: 2411: 2408: 2404: 2399: 2394: 2391: 2386: 2382: 2376: 2372: 2369: 2366: 2360: 2357: 2354: 2351: 2348: 2345: 2340: 2337: 2334: 2330: 2303: 2300: 2297: 2293: 2282: 2281: 2265: 2262: 2258: 2247: 2233: 2223: 2207: 2204: 2200: 2175: 2169: 2166: 2161: 2158: 2154: 2149: 2144: 2141: 2136: 2132: 2126: 2122: 2119: 2116: 2110: 2107: 2104: 2101: 2098: 2095: 2090: 2087: 2083: 2052: 2049: 2045: 2015: 2012: 2009: 2005: 1999: 1996: 1992: 1963: 1960: 1956: 1950: 1947: 1944: 1940: 1909: 1906: 1902: 1896: 1893: 1890: 1886: 1880: 1875: 1872: 1869: 1866: 1863: 1860: 1857: 1854: 1850: 1846: 1841: 1838: 1835: 1832: 1829: 1826: 1823: 1820: 1817: 1813: 1799: 1798: 1782: 1779: 1776: 1772: 1761: 1745: 1742: 1738: 1727: 1712: 1709: 1706: 1702: 1677: 1674: 1671: 1667: 1642: 1639: 1636: 1633: 1630: 1627: 1624: 1621: 1617: 1606: 1590: 1587: 1584: 1581: 1578: 1575: 1572: 1569: 1566: 1562: 1533: 1530: 1527: 1523: 1517: 1514: 1510: 1504: 1499: 1496: 1493: 1490: 1487: 1484: 1481: 1478: 1474: 1470: 1465: 1462: 1459: 1456: 1453: 1450: 1447: 1444: 1441: 1437: 1407: 1404: 1401: 1398: 1395: 1392: 1389: 1386: 1382: 1357: 1354: 1351: 1348: 1345: 1342: 1339: 1336: 1332: 1315: 1312: 1305: 1294: 1287: 1281: 1277: 1273: 1268: 1261: 1254: 1232: 1229: 1226: 1223: 1220: 1217: 1214: 1211: 1207: 1199: 1196: 1193: 1190: 1187: 1184: 1181: 1178: 1174: 1169: 1161: 1158: 1155: 1152: 1149: 1146: 1143: 1140: 1136: 1132: 1125: 1122: 1119: 1115: 1107: 1104: 1101: 1097: 1092: 1084: 1081: 1078: 1074: 1045: 1042: 1039: 1036: 1033: 1030: 1027: 1024: 1020: 1016: 1011: 1008: 1005: 1001: 970: 967: 964: 961: 958: 955: 952: 949: 945: 937: 934: 931: 928: 925: 922: 919: 916: 912: 907: 899: 896: 893: 890: 887: 884: 881: 878: 874: 870: 865: 862: 859: 856: 853: 850: 847: 844: 840: 812: 809: 806: 802: 794: 791: 788: 784: 779: 771: 768: 765: 761: 757: 752: 749: 746: 742: 726: 719: 710: 709: 695: 685: 671: 667: 656: 642: 632: 631:=Airflow (m/s) 618: 592: 588: 583: 579: 576: 573: 547: 544: 538: 537:Test procedure 535: 529: 526: 509: 506: 469: 466: 463: 460: 457: 454: 451: 448: 445: 441: 437: 434: 410: 407: 404: 401: 398: 395: 392: 388: 384: 381: 356: 350: 347: 344: 341: 338: 335: 332: 329: 326: 322: 318: 315: 309: 304: 301: 298: 295: 292: 289: 286: 282: 278: 275: 228:Ottawa, Canada 203: 200: 184:weatherization 121: 120: 35: 33: 26: 9: 6: 4: 3: 2: 5987: 5976: 5973: 5972: 5970: 5955: 5952: 5950: 5947: 5945: 5942: 5940: 5937: 5935: 5932: 5930: 5927: 5925: 5922: 5920: 5917: 5916: 5914: 5910: 5903: 5900: 5897: 5894: 5892: 5889: 5886: 5883: 5882: 5880: 5876: 5870: 5867: 5865: 5862: 5860: 5857: 5855: 5852: 5850: 5847: 5845: 5842: 5840: 5837: 5835: 5832: 5830: 5827: 5825: 5822: 5820: 5817: 5815: 5812: 5811: 5809: 5807:organizations 5803: 5797: 5794: 5792: 5789: 5787: 5784: 5782: 5779: 5777: 5774: 5772: 5769: 5767: 5764: 5762: 5759: 5757: 5754: 5752: 5751:Duct cleaning 5749: 5747: 5744: 5741: 5738: 5736: 5733: 5731: 5728: 5726: 5723: 5721: 5718: 5717: 5715: 5707: 5701: 5698: 5696: 5693: 5691: 5688: 5685: 5682: 5680: 5677: 5675: 5672: 5670: 5667: 5665: 5662: 5660: 5657: 5655: 5652: 5649: 5646: 5643: 5640: 5638: 5635: 5633: 5630: 5628: 5625: 5623: 5620: 5618: 5615: 5613: 5610: 5608: 5605: 5603: 5602:Control valve 5600: 5597: 5594: 5592: 5589: 5587: 5584: 5582: 5579: 5577: 5574: 5572: 5569: 5567: 5564: 5563: 5561: 5555: 5549: 5546: 5544: 5541: 5539: 5536: 5534: 5531: 5528: 5525: 5523: 5522:Turning vanes 5520: 5518: 5515: 5513: 5510: 5508: 5505: 5503: 5500: 5498: 5497:Thermal wheel 5495: 5493: 5490: 5488: 5485: 5483: 5480: 5478: 5475: 5473: 5470: 5468: 5465: 5463: 5462:Solar chimney 5460: 5458: 5455: 5453: 5450: 5448: 5445: 5443: 5440: 5438: 5435: 5433: 5430: 5428: 5425: 5423: 5420: 5418: 5415: 5413: 5410: 5408: 5405: 5403: 5400: 5398: 5395: 5393: 5390: 5388: 5385: 5383: 5380: 5378: 5375: 5373: 5370: 5368: 5365: 5363: 5360: 5358: 5355: 5353: 5350: 5348: 5345: 5343: 5340: 5338: 5335: 5333: 5330: 5328: 5325: 5323: 5320: 5318: 5315: 5313: 5310: 5308: 5305: 5303: 5300: 5298: 5295: 5293: 5290: 5288: 5285: 5283: 5280: 5278: 5275: 5273: 5270: 5268: 5265: 5263: 5260: 5258: 5255: 5253: 5250: 5248: 5245: 5243: 5240: 5238: 5235: 5233: 5232:Fan coil unit 5230: 5228: 5225: 5223: 5220: 5218: 5215: 5213: 5210: 5208: 5205: 5203: 5200: 5198: 5195: 5193: 5190: 5188: 5185: 5183: 5180: 5178: 5177:Cooling tower 5175: 5173: 5170: 5168: 5165: 5163: 5160: 5158: 5155: 5153: 5150: 5148: 5145: 5143: 5140: 5138: 5135: 5133: 5130: 5128: 5125: 5123: 5120: 5118: 5115: 5113: 5110: 5108: 5105: 5103: 5100: 5098: 5095: 5093: 5090: 5088: 5085: 5083: 5080: 5078: 5075: 5073: 5070: 5068: 5065: 5064: 5062: 5058: 5052: 5049: 5047: 5044: 5041: 5038: 5035: 5032: 5029: 5026: 5024: 5023:Vapor barrier 5021: 5019: 5016: 5014: 5011: 5009: 5006: 5004: 5001: 4999: 4998:Solar heating 4996: 4994: 4993:Solar cooling 4991: 4989: 4986: 4984: 4981: 4979: 4976: 4974: 4971: 4969: 4968:Refrigeration 4966: 4964: 4961: 4959: 4956: 4954: 4951: 4949: 4946: 4944: 4941: 4939: 4938:Passive house 4936: 4934: 4931: 4929: 4926: 4924: 4921: 4919: 4916: 4914: 4911: 4909: 4906: 4904: 4901: 4899: 4896: 4893: 4890: 4888: 4885: 4883: 4880: 4878: 4875: 4873: 4870: 4867: 4864: 4862: 4859: 4857: 4854: 4852: 4849: 4847: 4844: 4841: 4838: 4836: 4833: 4830: 4827: 4825: 4822: 4820: 4817: 4814: 4811: 4809: 4808:Chilled water 4806: 4804: 4801: 4799: 4796: 4794: 4791: 4789: 4786: 4784: 4781: 4779: 4776: 4774: 4771: 4769: 4766: 4764: 4761: 4759: 4756: 4754: 4751: 4750: 4748: 4744: 4738: 4735: 4733: 4730: 4728: 4725: 4723: 4720: 4718: 4715: 4713: 4710: 4708: 4707:Sensible heat 4705: 4703: 4700: 4698: 4695: 4693: 4690: 4688: 4687:Noise control 4685: 4683: 4680: 4678: 4675: 4673: 4670: 4668: 4667:Heat transfer 4665: 4663: 4660: 4658: 4655: 4653: 4650: 4648: 4645: 4643: 4640: 4638: 4635: 4633: 4630: 4628: 4625: 4623: 4620: 4618: 4615: 4614: 4612: 4606: 4602: 4595: 4590: 4588: 4583: 4581: 4576: 4575: 4572: 4564: 4559: 4548: 4547: 4539: 4531: 4525: 4523: 4521: 4512: 4508: 4504: 4500: 4496: 4492: 4488: 4481: 4474:(2): 801โ€“814. 4473: 4469: 4462: 4454: 4448: 4440: 4434: 4432: 4423: 4416: 4405: 4397: 4393: 4389: 4385: 4381: 4374: 4368: 4364: 4361: 4357: 4349: 4348: 4340: 4329: 4321: 4314: 4306: 4302: 4295: 4286: 4276: 4265: 4257: 4253: 4246: 4238: 4234: 4229: 4224: 4220: 4216: 4212: 4205: 4191:on 2015-04-02 4190: 4186: 4180: 4166:on 2015-04-14 4165: 4161: 4155: 4140: 4134: 4130: 4120: 4118: 4115: 4113: 4110: 4108: 4105: 4103: 4100: 4098: 4095: 4094: 4088: 4085: 4080: 4076: 4072: 4068: 4066: 4061: 4057: 4053: 4049: 4036: 4032: 4029: 4026: 4025:door fan test 4022: 4019: 4016: 4013: 4009: 4005: 4002: 3998: 3995: 3994: 3993: 3986: 3978: 3966: 3962: 3942: 3939: 3936: 3932: 3924: 3907: 3900: 3881: 3878: 3875: 3872: 3869: 3865: 3857: 3840: 3837: 3834: 3827: 3810: 3807: 3800: 3799: 3798: 3781: 3769: 3766: 3763: 3759: 3755: 3747: 3737: 3734: 3731: 3728: 3725: 3721: 3716: 3713: 3710: 3701: 3698: 3695: 3692: 3689: 3681: 3673: 3671: 3668: 3664: 3660: 3650: 3647: 3637: 3615: 3577: 3574: 3571: 3568: 3565: 3562: 3559: 3556: 3552: 3544: 3521: 3518: 3515: 3511: 3498: 3481: 3474: 3455: 3452: 3449: 3446: 3443: 3440: 3437: 3434: 3430: 3422: 3405: 3402: 3399: 3392: 3391: 3390: 3373: 3370: 3365: 3362: 3359: 3356: 3353: 3350: 3347: 3344: 3340: 3334: 3331: 3328: 3324: 3315: 3309: 3306: 3300: 3295: 3292: 3289: 3286: 3283: 3280: 3277: 3274: 3270: 3266: 3263: 3260: 3257: 3249: 3240: 3217: 3214: 3211: 3208: 3205: 3202: 3199: 3196: 3192: 3184: 3165: 3161: 3153: 3134: 3130: 3126: 3123: 3116: 3115: 3114: 3095: 3092: 3089: 3086: 3083: 3080: 3077: 3074: 3070: 3065: 3062: 3057: 3053: 3046: 3041: 3037: 3033: 3030: 3022: 3010: 3001: 2988: 2986: 2976: 2948: 2945: 2942: 2938: 2913: 2910: 2906: 2881: 2878: 2875: 2872: 2869: 2866: 2862: 2854: 2851: 2831: 2828: 2825: 2821: 2813: 2794: 2791: 2788: 2784: 2776: 2757: 2754: 2751: 2748: 2745: 2742: 2738: 2730: 2729: 2728: 2708: 2705: 2702: 2699: 2696: 2693: 2689: 2683: 2680: 2677: 2673: 2666: 2661: 2658: 2655: 2651: 2647: 2642: 2639: 2636: 2633: 2630: 2627: 2623: 2614: 2596: 2593: 2590: 2586: 2561: 2558: 2555: 2551: 2522: 2519: 2516: 2512: 2504: 2487: 2480: 2461: 2458: 2455: 2451: 2443: 2442: 2441: 2420: 2417: 2412: 2409: 2406: 2402: 2397: 2389: 2384: 2374: 2370: 2367: 2364: 2358: 2355: 2349: 2346: 2343: 2338: 2335: 2332: 2328: 2319: 2301: 2298: 2295: 2291: 2263: 2260: 2256: 2248: 2231: 2224: 2205: 2202: 2198: 2190: 2189: 2188: 2167: 2164: 2159: 2156: 2152: 2147: 2139: 2134: 2124: 2120: 2117: 2114: 2108: 2105: 2099: 2096: 2093: 2088: 2085: 2081: 2072: 2070: 2050: 2047: 2043: 2034: 2013: 2010: 2007: 2003: 1997: 1994: 1990: 1961: 1958: 1954: 1948: 1945: 1942: 1938: 1926: 1907: 1904: 1900: 1894: 1891: 1888: 1884: 1878: 1873: 1870: 1867: 1864: 1861: 1858: 1855: 1852: 1848: 1844: 1839: 1836: 1833: 1830: 1827: 1824: 1821: 1818: 1815: 1811: 1802: 1780: 1777: 1774: 1770: 1762: 1743: 1740: 1736: 1728: 1710: 1707: 1704: 1700: 1675: 1672: 1669: 1665: 1640: 1637: 1634: 1631: 1628: 1625: 1622: 1619: 1615: 1607: 1588: 1585: 1582: 1579: 1576: 1573: 1570: 1567: 1564: 1560: 1552: 1551: 1550: 1531: 1528: 1525: 1521: 1515: 1512: 1508: 1502: 1497: 1494: 1491: 1488: 1485: 1482: 1479: 1476: 1472: 1468: 1463: 1460: 1457: 1454: 1451: 1448: 1445: 1442: 1439: 1435: 1426: 1423: 1405: 1402: 1399: 1396: 1393: 1390: 1387: 1384: 1380: 1355: 1352: 1349: 1346: 1343: 1340: 1337: 1334: 1330: 1321: 1311: 1299: 1249: 1230: 1227: 1224: 1221: 1218: 1215: 1212: 1209: 1205: 1197: 1194: 1191: 1188: 1185: 1182: 1179: 1176: 1172: 1159: 1156: 1153: 1150: 1147: 1144: 1141: 1138: 1134: 1130: 1123: 1120: 1117: 1113: 1105: 1102: 1099: 1095: 1082: 1079: 1076: 1072: 1063: 1060: 1043: 1040: 1037: 1034: 1031: 1028: 1025: 1022: 1018: 1014: 1009: 1006: 1003: 999: 990: 987: 968: 965: 962: 959: 956: 953: 950: 947: 943: 935: 932: 929: 926: 923: 920: 917: 914: 910: 897: 894: 891: 888: 885: 882: 879: 876: 872: 868: 863: 860: 857: 854: 851: 848: 845: 842: 838: 829: 810: 807: 804: 800: 792: 789: 786: 782: 769: 766: 763: 759: 755: 750: 747: 744: 740: 731: 714: 693: 686: 669: 657: 640: 633: 616: 609: 608: 607: 590: 586: 577: 574: 571: 563: 561: 552: 543: 534: 525: 523: 514: 505: 503: 499: 494: 490: 485: 467: 464: 461: 458: 455: 452: 449: 446: 443: 439: 435: 432: 424: 408: 405: 402: 399: 396: 393: 390: 386: 382: 379: 371: 354: 348: 345: 342: 339: 336: 333: 330: 327: 324: 320: 316: 313: 307: 302: 299: 296: 293: 290: 287: 284: 280: 276: 273: 265: 261: 258: 256: 250: 248: 244: 240: 236: 231: 229: 225: 224:blower window 220: 218: 214: 210: 199: 197: 193: 189: 185: 179: 177: 173: 169: 167: 163: 159: 155: 150: 148: 144: 140: 136: 127: 117: 114: 106: 95: 92: 88: 85: 81: 78: 74: 71: 67: 64: โ€“  63: 62:"Blower door" 59: 58:Find sources: 52: 48: 42: 41: 36:This article 34: 30: 25: 24: 19: 5929:Fireproofing 5713:and services 5709:Professions, 5607:Gas detector 5580: 5507:Trickle vent 5482:Smoke damper 5477:Smoke canopy 5472:Space heater 5402:Plenum space 5337:Heating film 5217:Exhaust hood 5187:Dehumidifier 5127:Blast damper 5122:Barrier pipe 5097:Air purifier 5008:Thermosiphon 4887:Free cooling 4803:Chilled beam 4727:Thermal mass 4712:Stack effect 4697:Particulates 4677:Infiltration 4608:Fundamental 4558: 4545: 4538: 4529: 4494: 4490: 4480: 4471: 4467: 4461: 4452: 4447: 4438: 4421: 4415: 4404: 4390:(1): 81โ€“86. 4387: 4383: 4373: 4356: 4346: 4339: 4328: 4319: 4313: 4304: 4300: 4294: 4285: 4275: 4264: 4255: 4251: 4245: 4218: 4214: 4204: 4193:. Retrieved 4189:the original 4179: 4168:. Retrieved 4164:the original 4154: 4143:. Retrieved 4133: 4097:Energy audit 4083: 4081: 4077: 4073: 4069: 4064: 4046: 4024: 3991: 3972:Applications 3682: 3679: 3656: 3648: 3597: 3250: 3246: 3237: 3023: 3016: 3007: 2994: 2981: 2848:= Reference 2615: 2542: 2320: 2283: 2073: 2035: 1927: 1803: 1800: 1427: 1424: 1317: 1300: 1280:. Typical โˆ†P 1250: 1064: 1061: 991: 988: 830: 732: 715: 711: 564: 557: 540: 531: 519: 486: 425: 372: 266: 262: 259: 255:retrofitting 251: 232: 223: 221: 205: 180: 172:Airtightness 170: 151: 134: 132: 109: 103:October 2023 100: 90: 83: 76: 69: 57: 45:Please help 40:verification 37: 5975:Ventilation 5939:Warm Spaces 5581:Blower door 5559:and control 5557:Measurement 5538:Windcatcher 5512:Trombe wall 5452:Sail switch 5432:Refrigerant 5427:Recuperator 5302:Grease duct 5262:Freeze stat 5247:Fire damper 5117:Back boiler 5087:Air ionizer 5082:Air handler 5046:Ventilation 4898:Hybrid heat 4763:Air barrier 4682:Latent heat 2850:air density 1928:The values 1320:air density 1282:n, Building 1278:n, Building 245:at 50  196:ventilation 135:blower door 5695:Thermostat 5617:Humidistat 5548:Zone valve 5517:TurboSwing 5392:Oil heater 5362:Humidifier 5292:Gas heater 5242:Fan heater 5212:Evaporator 5197:Economizer 5172:Compressor 5077:Air filter 5060:Components 4877:Forced-air 4773:Antifreeze 4746:Technology 4692:Outgassing 4632:Convection 4307:: 521โ€“534. 4215:Indoor Air 4195:2015-03-29 4170:2015-03-29 4145:2015-03-29 4126:References 528:Test setup 239:Harold Orr 73:newspapers 5805:Industry 5654:OpenTherm 5332:Heat pump 5327:Heat pipe 5277:Fume hood 5252:Fireplace 5157:Condenser 5107:Attic fan 4903:Hydronics 4511:120271786 4237:110498827 3963:(98  3748:∗ 3702:∗ 3640:Reference 3618:Reference 3507:Δ 3482:ρ 3371:− 3320:Δ 3316:∗ 3307:ρ 3301:∗ 3063:∗ 2939:ρ 2907:ρ 2863:ρ 2822:ρ 2690:ρ 2674:ρ 2667:∗ 2452:ρ 2390:∗ 2368:∗ 2365:0.0035666 2359:− 2350:∗ 2329:ρ 2292:ρ 2199:ρ 2140:∗ 2118:∗ 2115:0.0035666 2109:− 2100:∗ 2082:ρ 2044:ρ 2004:ρ 1991:ρ 1955:ρ 1939:ρ 1901:ρ 1885:ρ 1879:∗ 1771:ρ 1737:ρ 1522:ρ 1509:ρ 1503:∗ 1168:Δ 1091:Δ 906:Δ 778:Δ 666:Δ 582:Δ 560:power law 522:manometer 166:manometer 5969:Category 5912:See also 5637:LonWorks 5571:Aquastat 5437:Register 5417:Radiator 5072:Air door 4872:Firestop 4672:Humidity 4647:Enthalpy 4637:Dilution 4622:Bake-out 4610:concepts 4363:Archived 4258:: 41โ€“57. 4091:See also 3631:Building 3624:Building 3609:Building 3602:Building 2069:IP units 1306:Building 1295:Building 1288:Building 727:Building 18:Air door 5711:trades, 5282:Furnace 5147:Chiller 4819:Coolant 3667:tobacco 2347:0.07517 2097:0.07517 202:History 186:crews, 139:airflow 87:scholar 5864:SMACNA 5824:ASHRAE 5644:(MERV) 5598:(CADR) 5576:BACnet 5529:(ULPA) 5382:Louver 5307:Grille 5182:Damper 5132:Boiler 5030:(VCRS) 4831:(DOAS) 4509:  4303:. II. 4235:  4038:leaks. 4012:ASHRAE 3961:metres 2985:Pascal 2385:5.2553 2135:5.2553 1276:and โˆ†P 1274:n, Fan 493:ASHRAE 154:blower 89:  82:  75:  68:  60:  5904:(VOC) 5898:(SBS) 5887:(IAQ) 5844:CIBSE 5839:BSRIA 5742:(BIM) 5686:(STP) 5650:(NTP) 5272:Freon 5042:(VRF) 5036:(VAV) 4894:(HRV) 4868:(ERV) 4842:(DCV) 4815:(CAV) 4550:(PDF) 4507:S2CID 4280:1975. 4254:. 9. 4233:S2CID 4065:clean 4034:only. 3670:smoke 3644:Force 3540:Force 209:Texas 94:JSTOR 80:books 5859:LEED 5819:AMCA 5814:AHRI 5347:HEPA 5267:Flue 5192:Duct 4048:NFPA 4021:NFPA 4010:and 4008:IECC 3699:1000 3659:LEED 3627:and 3605:and 2578:and 1980:and 1692:and 1291:and 1258:and 66:news 5869:UMC 5854:IIR 5834:BRE 5227:Fan 4499:doi 4495:114 4472:109 4392:doi 4223:doi 4056:ISO 3782:0.3 3374:0.5 3021:). 2421:460 2398:528 2375:528 2168:460 2148:528 2125:528 1269:Fan 1262:Fan 1255:Fan 730:). 720:Fan 524:). 243:ach 158:fan 156:or 49:by 5971:: 4519:^ 4505:. 4493:. 4489:. 4470:. 4430:^ 4388:10 4386:. 4382:. 4305:85 4256:85 4231:. 4217:. 4213:. 4060:EN 4058:, 3967:)) 3965:in 3614:SI 3166:50 3135:50 3066:60 3058:50 3042:50 3019:50 2998:50 2996:(Q 504:. 450:50 355:20 331:50 249:. 247:Pa 149:. 133:A 4593:e 4586:t 4579:v 4513:. 4501:: 4398:. 4394:: 4239:. 4225:: 4219:5 4198:. 4173:. 4148:. 4014:. 3943:f 3940:e 3937:R 3933:H 3908:H 3882:r 3879:o 3876:o 3873:l 3870:F 3866:A 3841:A 3838:L 3835:E 3811:L 3808:N 3778:) 3770:f 3767:e 3764:R 3760:H 3756:H 3751:( 3745:) 3738:r 3735:o 3732:o 3729:l 3726:F 3722:A 3717:A 3714:L 3711:E 3705:( 3696:= 3693:L 3690:N 3629:n 3622:C 3607:n 3600:C 3578:g 3575:n 3572:i 3569:d 3566:l 3563:i 3560:u 3557:B 3553:n 3522:f 3519:e 3516:R 3512:P 3456:g 3453:n 3450:i 3447:d 3444:l 3441:i 3438:u 3435:B 3431:C 3406:A 3403:L 3400:E 3366:g 3363:n 3360:i 3357:d 3354:l 3351:i 3348:u 3345:B 3341:n 3335:f 3332:e 3329:R 3325:P 3310:2 3296:g 3293:n 3290:i 3287:d 3284:l 3281:i 3278:u 3275:B 3271:C 3267:= 3264:A 3261:L 3258:E 3218:g 3215:n 3212:i 3209:d 3206:l 3203:i 3200:u 3197:B 3193:V 3162:Q 3131:H 3127:C 3124:A 3096:g 3093:n 3090:i 3087:d 3084:l 3081:i 3078:u 3075:B 3071:V 3054:Q 3047:= 3038:H 3034:C 3031:A 2949:t 2946:u 2943:O 2914:n 2911:I 2882:l 2879:a 2876:u 2873:t 2870:c 2867:A 2832:f 2829:e 2826:R 2795:n 2792:a 2789:F 2785:Q 2758:l 2755:a 2752:u 2749:t 2746:c 2743:A 2739:Q 2709:l 2706:a 2703:u 2700:t 2697:c 2694:A 2684:f 2681:e 2678:R 2662:n 2659:a 2656:F 2652:Q 2648:= 2643:l 2640:a 2637:u 2634:t 2631:c 2628:A 2624:Q 2597:n 2594:a 2591:F 2587:n 2562:n 2559:a 2556:F 2552:C 2523:t 2520:u 2517:O 2513:T 2488:E 2462:t 2459:u 2456:O 2427:) 2418:+ 2413:t 2410:u 2407:O 2403:T 2393:( 2381:) 2371:E 2356:1 2353:( 2344:= 2339:t 2336:u 2333:O 2302:t 2299:u 2296:O 2264:n 2261:I 2257:T 2232:E 2206:n 2203:I 2174:) 2165:+ 2160:n 2157:I 2153:T 2143:( 2131:) 2121:E 2106:1 2103:( 2094:= 2089:n 2086:I 2051:n 2048:I 2014:t 2011:u 2008:O 1998:n 1995:I 1962:n 1959:I 1949:t 1946:u 1943:O 1908:n 1905:I 1895:t 1892:u 1889:O 1874:d 1871:e 1868:r 1865:u 1862:s 1859:a 1856:e 1853:M 1849:Q 1845:= 1840:d 1837:e 1834:t 1831:c 1828:e 1825:r 1822:r 1819:o 1816:C 1812:Q 1781:t 1778:u 1775:O 1744:n 1741:I 1711:n 1708:a 1705:F 1701:n 1676:n 1673:a 1670:F 1666:C 1641:d 1638:e 1635:r 1632:u 1629:s 1626:a 1623:e 1620:M 1616:Q 1589:d 1586:e 1583:t 1580:c 1577:e 1574:r 1571:r 1568:o 1565:C 1561:Q 1532:t 1529:u 1526:O 1516:n 1513:I 1498:d 1495:e 1492:r 1489:u 1486:s 1483:a 1480:e 1477:M 1473:Q 1469:= 1464:d 1461:e 1458:t 1455:c 1452:e 1449:r 1446:r 1443:o 1440:C 1436:Q 1406:g 1403:n 1400:i 1397:d 1394:l 1391:i 1388:u 1385:B 1381:n 1356:g 1353:n 1350:i 1347:d 1344:l 1341:i 1338:u 1335:B 1331:C 1304:n 1293:n 1286:C 1267:Q 1260:n 1253:C 1231:g 1228:n 1225:i 1222:d 1219:l 1216:i 1213:u 1210:B 1206:n 1198:g 1195:n 1192:i 1189:d 1186:l 1183:i 1180:u 1177:B 1173:P 1160:g 1157:n 1154:i 1151:d 1148:l 1145:i 1142:u 1139:B 1135:C 1131:= 1124:n 1121:a 1118:F 1114:n 1106:n 1103:a 1100:F 1096:P 1083:n 1080:a 1077:F 1073:C 1044:g 1041:n 1038:i 1035:d 1032:l 1029:i 1026:u 1023:B 1019:Q 1015:= 1010:n 1007:a 1004:F 1000:Q 969:g 966:n 963:i 960:d 957:l 954:i 951:u 948:B 944:n 936:g 933:n 930:i 927:d 924:l 921:i 918:u 915:B 911:P 898:g 895:n 892:i 889:d 886:l 883:i 880:u 877:B 873:C 869:= 864:g 861:n 858:i 855:d 852:l 849:i 846:u 843:B 839:Q 811:n 808:a 805:F 801:n 793:n 790:a 787:F 783:P 770:n 767:a 764:F 760:C 756:= 751:n 748:a 745:F 741:Q 725:Q 718:Q 694:n 670:P 641:C 617:Q 591:n 587:P 578:C 575:= 572:Q 468:l 465:a 462:c 459:s 456:a 453:p 447:t 444:a 440:H 436:C 433:A 409:l 406:a 403:r 400:u 397:t 394:a 391:n 387:H 383:C 380:A 349:l 346:a 343:c 340:s 337:a 334:p 328:t 325:a 321:H 317:C 314:A 308:= 303:l 300:a 297:r 294:u 291:t 288:a 285:n 281:H 277:C 274:A 116:) 110:( 105:) 101:( 91:ยท 84:ยท 77:ยท 70:ยท 43:. 20:.

Index

Air door

verification
improve this article
adding citations to reliable sources
"Blower door"
news
newspapers
books
scholar
JSTOR
Learn how and when to remove this message

airflow
ductwork airtightness
building envelope
blower
fan
pressure measurement
manometer
Airtightness
General Services Administration
weatherization
home performance
energy auditors
ventilation
Texas
Princeton University
Twin Rivers, New Jersey
Ottawa, Canada

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.

โ†‘