Droop speed control

Source 📝

124:
mover speed is fixed by the grid, this difference in speed reference and actual speed of the prime mover is used to increase the flow of working fluid (fuel, steam, etc.) to the prime mover, and hence power output is increased. The reverse will be true for decreasing power output. The prime mover speed reference is always greater than actual speed of the prime mover. The actual speed of the prime mover is allowed to "droop" or decrease with respect to the reference, and so the name.
320:
referred to as "straight proportional" control. If the entire grid tends to be overloaded, the grid frequency and hence actual speed of generator will decrease. All units will see an increase in the speed error, and so increase fuel flow to their prime movers and power output. In this way droop speed control mode also helps to hold a stable grid frequency. The amount of power produced is strictly proportional to the error between the actual turbine speed and speed reference.
726: 381: 1305: 38:. It works by controlling the rate of power produced by the prime mover according to the grid frequency. With droop speed control, when the grid is operating at maximum operating frequency, the prime mover's power is reduced to zero, and when the grid is at minimum operating frequency, the power is set to 100%, and intermediate values at other operating frequencies. 123:
A speed reference as percentage of actual speed is set in this mode. As the generator is loaded from no load to full load, the actual speed of the prime mover tends to decrease. In order to increase the power output in this mode, the prime mover speed reference is increased. Because the actual prime
119:
The frequency (F) of a synchronous generator is directly proportional to its speed (N). When multiple synchronous generators are connected in parallel to the electrical grid, the frequency is fixed by the grid, since individual power output of each generator will be small compared to the load on a
319:
As frequency is fixed on the grid, and so actual turbine speed is also fixed, the increase in turbine speed reference will increase the error between reference and actual speed. As the difference increases, fuel flow is increased to increase power output, and vice versa. This type of control is
315:
In this case, speed reference will be 104% and actual speed will be 100%. For every 1% change in the turbine speed reference, the power output of the turbine will change by 25% of rated for a unit with a 4% droop setting. Droop is therefore expressed as the percentage change in (design) speed
376:
adjustment, or the analogous operation for an electronic speed governor. All units to be connected to a grid should have the same droop setting, so that all plants respond in the same way to the instantaneous changes in frequency without depending on outside communication.
302: 367:
of the total rotating mass of all generators and motors running on the grid. Adjustments in power output for a particular primer mover and generator combination are made by slowly raising the droop curve by increasing the spring pressure on a
44:
In practice, the droop curves that are used by generators on large electrical grids are not necessarily linear or the same, and may be adjusted by operators. This permits the ratio of power used to vary depending on load, so for example,
52:
Droop speed control can also be used by grid storage systems. With droop speed control those systems will remove energy from the grid at higher than average frequencies, and supply it at lower frequencies.
388:
Next to the inertia given by the parallel operation of synchronous generators, the frequency speed droop is the primary instantaneous parameter in control of an individual power plant's power output (
22:
is a control mode used for AC electrical power generators, whereby the power output of a generator reduces as the line frequency increases. It is commonly used as the speed control mode of the
49:
generators will generate a larger proportion at low demand. Stability requires that over the operating frequency range the power output is a monotonically decreasing function of frequency.
133: 127:
For example, if the turbine is rated at 3000 rpm, and the machine speed reduces from 3000 rpm to 2880 rpm when it is loaded from no load to base load, then the droop % is given by
360:
of North America, power plants typically operate with a four or five percent speed droop. By definition, with 5% droop the full-load speed is 100% and the no-load speed is 105%.
100: 323:
It can be mathematically shown that if all machines synchronized to a system have the same droop speed control, they will share load proportionate to the machine ratings.
120:
large grid. Synchronous generators connected to the grid run at various speeds but they all run at the same frequency because they differ in the number of poles (P).
41:
This mode allows synchronous generators to run in parallel, so that loads are shared among generators with the same droop curve in proportion to their power rating.
547: 473: 353:
Multiple synchronous generators having equal % droop setting connected to a grid will share the change in grid load in proportion of their base load.
577: 1250: 527: 1308: 725: 1147: 326:
For example, how fuel flow is increased or decreased in a GE-design heavy duty gas turbine can be given by the formula,
1329: 1255: 570: 875: 439: 297:{\displaystyle \mathrm {Droop\%} ={\frac {\mathrm {No\ load\ speed-Full\ load\ speed} }{\mathrm {No\ load\ speed} }}} 1038: 963: 834: 411: 477: 384:
Contiguous United States power transmission grid consists of 300,000 km of lines operated by 500 companies.
1210: 1142: 1132: 1008: 908: 563: 1063: 1023: 600: 1290: 1285: 1003: 978: 968: 944: 939: 645: 401: 67: 1205: 923: 893: 670: 406: 1260: 749: 710: 1235: 1043: 983: 640: 1174: 1164: 1154: 1095: 958: 741: 630: 1230: 998: 993: 973: 31: 27: 824: 586: 369: 8: 1195: 1028: 928: 903: 856: 665: 655: 373: 1069: 680: 1220: 1100: 705: 523: 435: 23: 1169: 1110: 814: 809: 786: 695: 635: 1200: 1159: 1137: 1018: 988: 953: 913: 715: 357: 35: 1225: 1215: 1013: 625: 350:
The above formula is nothing but the equation of a straight line (y = mx + b).
1323: 1245: 1033: 918: 898: 829: 819: 776: 660: 615: 497:
Speed Droop and Power Generation. Application Note 01302. 2. Woodward. Speed
1265: 1240: 1105: 1074: 888: 690: 552:. International Journal of Distributed Energy Resources, Vol 1, No 1, 2005. 506: 452: 335:
FSRN = Fuel Stroke Reference (Fuel supplied to Gas Turbine) for droop mode
1090: 1058: 851: 839: 759: 685: 675: 605: 380: 1053: 1048: 861: 844: 700: 555: 769: 764: 650: 610: 46: 883: 804: 794: 364: 799: 754: 522:. Boca Raton, Florida: Taylor and Francis. p. 35. 389: 136: 70: 61:
The frequency of a synchronous generator is given by
296: 94: 1321: 432:Elements of Power System Analysis Third Edition 363:Normally the changes in speed are minor due to 571: 549:Applicability of droops in low voltage grids 474:"Real Time Frequency Data - Last 60 Minutes" 578: 564: 585: 517: 379: 1322: 559: 329:FSRN = (FSKRN2 * (TNR-TNH)) + FSKRN1 16:Control mode for AC power generators 316:required for 100% governor action. 95:{\displaystyle F={\frac {PN}{120}}} 13: 1256:Renewable energy commercialization 540: 288: 285: 282: 279: 276: 270: 267: 264: 261: 255: 252: 247: 244: 241: 238: 235: 229: 226: 223: 220: 214: 211: 208: 205: 199: 196: 193: 190: 187: 181: 178: 175: 172: 166: 163: 153: 150: 147: 144: 141: 138: 14: 1341: 1304: 1303: 724: 476:. National Grid. Archived from 434:, McGraw-Hill, New York (1975) 412:Dynamic demand (electric power) 511: 500: 491: 466: 445: 424: 338:TNR = Turbine Speed Reference 115:N, speed of generator (in RPM) 1: 1251:Renewable Energy Certificates 1211:Cost of electricity by source 1133:Arc-fault circuit interrupter 1009:High-voltage shore connection 417: 1266:Spark/Dark/Quark/Bark spread 1064:Transmission system operator 1024:Mains electricity by country 601:Automatic generation control 356:For stable operation of the 7: 1291:List of electricity sectors 1286:Electric energy consumption 1004:High-voltage direct current 979:Electric power transmission 969:Electric power distribution 646:Energy return on investment 518:Whitaker, Jerry C. (2006). 402:Electric power transmission 395: 341:TNH = Actual Turbine Speed 10: 1346: 1206:Carbon offsets and credits 924:Three-phase electric power 430:William D. Stevenson, Jr. 407:Wide area synchronous grid 1330:Electric power generation 1299: 1274: 1261:Renewable Energy Payments 1184: 1121: 1083: 937: 874: 785: 750:Fossil fuel power station 740: 733: 722: 593: 520:AC power systems handbook 56: 1044:Single-wire earth return 984:Electrical busbar system 641:Energy demand management 1175:Residual-current device 1165:Power system protection 1155:Generator interlock kit 959:Distributed generation 631:Electric power quality 385: 308:= (3000 – 2880) / 3000 298: 96: 1231:Fossil fuel phase-out 999:Electricity retailing 994:Electrical substation 974:Electric power system 383: 299: 109:F, frequency (in Hz), 97: 32:synchronous generator 587:Electricity delivery 370:centrifugal governor 134: 68: 1196:Availability factor 1148:Sulfur hexafluoride 1029:Overhead power line 929:Virtual power plant 904:Induction generator 857:Sustainable biofuel 666:Home energy storage 656:Grid energy storage 621:Droop speed control 374:engine control unit 112:P, number of poles, 20:Droop speed control 1070:Transmission tower 681:Nameplate capacity 453:"Governor Control" 386: 347:FSKRN1 = Constant 344:FSKRN2 = Constant 294: 92: 1317: 1316: 1221:Environmental tax 1101:Cascading failure 870: 869: 706:Utility frequency 529:978-0-8493-4034-5 292: 275: 260: 234: 219: 186: 171: 90: 1337: 1307: 1306: 1216:Energy subsidies 1170:Protective relay 1111:Rolling blackout 738: 737: 728: 696:Power-flow study 636:Electrical fault 580: 573: 566: 557: 556: 534: 533: 515: 509: 504: 498: 495: 489: 488: 486: 485: 470: 464: 463: 461: 460: 449: 443: 428: 303: 301: 300: 295: 293: 291: 273: 258: 250: 232: 217: 184: 169: 161: 156: 101: 99: 98: 93: 91: 86: 78: 34:connected to an 1345: 1344: 1340: 1339: 1338: 1336: 1335: 1334: 1320: 1319: 1318: 1313: 1295: 1279: 1277: 1270: 1201:Capacity factor 1189: 1187: 1180: 1160:Numerical relay 1138:Circuit breaker 1126: 1124: 1117: 1079: 1019:Load management 989:Electrical grid 954:Demand response 947: 942: 933: 914:Microgeneration 866: 781: 729: 720: 716:Vehicle-to-grid 589: 584: 546:Alfred Engler: 543: 541:Further reading 538: 537: 530: 516: 512: 505: 501: 496: 492: 483: 481: 472: 471: 467: 458: 456: 451: 450: 446: 429: 425: 420: 398: 358:electrical grid 251: 162: 160: 137: 135: 132: 131: 79: 77: 69: 66: 65: 59: 36:electrical grid 17: 12: 11: 5: 1343: 1333: 1332: 1315: 1314: 1312: 1311: 1300: 1297: 1296: 1294: 1293: 1288: 1282: 1280: 1276:Statistics and 1275: 1272: 1271: 1269: 1268: 1263: 1258: 1253: 1248: 1243: 1238: 1233: 1228: 1226:Feed-in tariff 1223: 1218: 1213: 1208: 1203: 1198: 1192: 1190: 1185: 1182: 1181: 1179: 1178: 1172: 1167: 1162: 1157: 1152: 1151: 1150: 1145: 1135: 1129: 1127: 1122: 1119: 1118: 1116: 1115: 1114: 1113: 1103: 1098: 1093: 1087: 1085: 1081: 1080: 1078: 1077: 1072: 1067: 1061: 1056: 1051: 1046: 1041: 1036: 1031: 1026: 1021: 1016: 1014:Interconnector 1011: 1006: 1001: 996: 991: 986: 981: 976: 971: 966: 964:Dynamic demand 961: 956: 950: 948: 938: 935: 934: 932: 931: 926: 921: 916: 911: 906: 901: 896: 894:Combined cycle 891: 886: 880: 878: 872: 871: 868: 867: 865: 864: 859: 854: 849: 848: 847: 842: 837: 832: 827: 817: 812: 807: 802: 797: 791: 789: 783: 782: 780: 779: 774: 773: 772: 767: 762: 757: 746: 744: 735: 731: 730: 723: 721: 719: 718: 713: 708: 703: 698: 693: 688: 683: 678: 673: 671:Load-following 668: 663: 658: 653: 648: 643: 638: 633: 628: 626:Electric power 623: 618: 613: 608: 603: 597: 595: 591: 590: 583: 582: 575: 568: 560: 554: 553: 542: 539: 536: 535: 528: 510: 499: 490: 465: 444: 422: 421: 419: 416: 415: 414: 409: 404: 397: 394: 313: 312: 309: 305: 304: 290: 287: 284: 281: 278: 272: 269: 266: 263: 257: 254: 249: 246: 243: 240: 237: 231: 228: 225: 222: 216: 213: 210: 207: 204: 201: 198: 195: 192: 189: 183: 180: 177: 174: 168: 165: 159: 155: 152: 149: 146: 143: 140: 117: 116: 113: 110: 103: 102: 89: 85: 82: 76: 73: 58: 55: 15: 9: 6: 4: 3: 2: 1342: 1331: 1328: 1327: 1325: 1310: 1302: 1301: 1298: 1292: 1289: 1287: 1284: 1283: 1281: 1273: 1267: 1264: 1262: 1259: 1257: 1254: 1252: 1249: 1247: 1246:Pigouvian tax 1244: 1242: 1239: 1237: 1234: 1232: 1229: 1227: 1224: 1222: 1219: 1217: 1214: 1212: 1209: 1207: 1204: 1202: 1199: 1197: 1194: 1193: 1191: 1183: 1176: 1173: 1171: 1168: 1166: 1163: 1161: 1158: 1156: 1153: 1149: 1146: 1144: 1143:Earth-leakage 1141: 1140: 1139: 1136: 1134: 1131: 1130: 1128: 1120: 1112: 1109: 1108: 1107: 1104: 1102: 1099: 1097: 1094: 1092: 1089: 1088: 1086: 1084:Failure modes 1082: 1076: 1073: 1071: 1068: 1065: 1062: 1060: 1057: 1055: 1052: 1050: 1047: 1045: 1042: 1040: 1037: 1035: 1034:Power station 1032: 1030: 1027: 1025: 1022: 1020: 1017: 1015: 1012: 1010: 1007: 1005: 1002: 1000: 997: 995: 992: 990: 987: 985: 982: 980: 977: 975: 972: 970: 967: 965: 962: 960: 957: 955: 952: 951: 949: 946: 941: 936: 930: 927: 925: 922: 920: 919:Rankine cycle 917: 915: 912: 910: 907: 905: 902: 900: 899:Cooling tower 897: 895: 892: 890: 887: 885: 882: 881: 879: 877: 873: 863: 860: 858: 855: 853: 850: 846: 843: 841: 838: 836: 833: 831: 828: 826: 823: 822: 821: 818: 816: 813: 811: 808: 806: 803: 801: 798: 796: 793: 792: 790: 788: 784: 778: 775: 771: 768: 766: 763: 761: 758: 756: 753: 752: 751: 748: 747: 745: 743: 742:Non-renewable 739: 736: 732: 727: 717: 714: 712: 709: 707: 704: 702: 699: 697: 694: 692: 689: 687: 684: 682: 679: 677: 674: 672: 669: 667: 664: 662: 661:Grid strength 659: 657: 654: 652: 649: 647: 644: 642: 639: 637: 634: 632: 629: 627: 624: 622: 619: 617: 616:Demand factor 614: 612: 609: 607: 604: 602: 599: 598: 596: 592: 588: 581: 576: 574: 569: 567: 562: 561: 558: 551: 550: 545: 544: 531: 525: 521: 514: 508: 507:VSYNC-Project 503: 494: 480:on 2015-12-24 479: 475: 469: 455:. Control.com 454: 448: 441: 440:0-07-061285-4 437: 433: 427: 423: 413: 410: 408: 405: 403: 400: 399: 393: 391: 382: 378: 375: 371: 366: 361: 359: 354: 351: 348: 345: 342: 339: 336: 333: 330: 327: 324: 321: 317: 310: 307: 306: 202: 157: 130: 129: 128: 125: 121: 114: 111: 108: 107: 106: 87: 83: 80: 74: 71: 64: 63: 62: 54: 50: 48: 42: 39: 37: 33: 29: 25: 21: 1241:Net metering 1188:and policies 1106:Power outage 1075:Utility pole 1039:Pumped hydro 945:distribution 940:Transmission 889:Cogeneration 691:Power factor 620: 548: 519: 513: 502: 493: 482:. Retrieved 478:the original 468: 457:. Retrieved 447: 442:page 378-379 431: 426: 387: 362: 355: 352: 349: 346: 343: 340: 337: 334: 331: 328: 325: 322: 318: 314: 126: 122: 118: 104: 60: 51: 43: 40: 19: 18: 1236:Load factor 1091:Black start 1059:Transformer 760:Natural gas 711:Variability 686:Peak demand 676:Merit order 606:Backfeeding 28:prime mover 1278:production 1123:Protective 1054:Super grid 1049:Smart grid 876:Generation 810:Geothermal 701:Repowering 484:2015-12-24 459:2015-12-24 418:References 30:driving a 1186:Economics 909:Micro CHP 787:Renewable 770:Petroleum 765:Oil shale 651:Grid code 611:Base load 372:or by an 203:− 154:% 47:base load 1324:Category 1309:Category 1096:Brownout 884:AC power 594:Concepts 396:See also 24:governor 1125:devices 835:Thermal 830:Osmotic 825:Current 805:Biomass 795:Biofuel 777:Nuclear 734:Sources 365:inertia 332:Where, 820:Marine 800:Biogas 526:  438:  274:  259:  233:  218:  185:  170:  105:where 57:Linear 1177:(GFI) 1066:(TSO) 852:Solar 840:Tidal 815:Hydro 26:of a 943:and 862:Wind 845:Wave 755:Coal 524:ISBN 436:ISBN 311:= 4% 392:). 88:120 1326:: 390:kW 579:e 572:t 565:v 532:. 487:. 462:. 289:d 286:e 283:e 280:p 277:s 271:d 268:a 265:o 262:l 256:o 253:N 248:d 245:e 242:e 239:p 236:s 230:d 227:a 224:o 221:l 215:l 212:l 209:u 206:F 200:d 197:e 194:e 191:p 188:s 182:d 179:a 176:o 173:l 167:o 164:N 158:= 151:p 148:o 145:o 142:r 139:D 84:N 81:P 75:= 72:F

Index

governor
prime mover
synchronous generator
electrical grid
base load
electrical grid
inertia
centrifugal governor
engine control unit

kW
Electric power transmission
Wide area synchronous grid
Dynamic demand (electric power)
ISBN
0-07-061285-4
"Governor Control"
"Real Time Frequency Data - Last 60 Minutes"
the original
VSYNC-Project
ISBN
978-0-8493-4034-5
Applicability of droops in low voltage grids
v
t
e
Electricity delivery
Automatic generation control
Backfeeding
Base load

Text is available under the Creative Commons Attribution-ShareAlike License. Additional terms may apply.