602:"Water spray" systems are operationally identical to a deluge system, but the piping and discharge nozzle spray patterns are designed to protect a uniquely configured hazard, usually being three-dimensional components or equipment (i.e. as opposed to a deluge system, which is designed to cover the horizontal floor area of a room). The nozzles used may not be listed fire sprinklers, and are usually selected for a specific spray pattern to conform to the three-dimensional nature of the hazard (e.g. typical spray patterns being oval, fan, full circle, narrow jet). Examples of hazards protected by water spray systems are electrical transformers containing oil for cooling or turbo-generator bearings. Water spray systems can also be used externally on the surfaces of tanks containing flammable liquids or gases (such as hydrogen). Here the water spray is intended to cool the tank and its contents to prevent tank rupture/explosion ( 355: 1657: 828:
sprinklers that would operate in the design area. This includes pressure losses due to friction inside the piping and losses or gains due to elevational differences between the source and the discharging sprinklers. Sometimes momentum pressure from water velocity inside the piping is also calculated. Typically these calculations are performed using computer software, but before the advent of computer systems these sometimes complicated calculations were performed by hand. This skill of calculating sprinkler systems by hand is still required training for a sprinkler system design
570:
pre-action valve which is a mechanically latched valve (i.e. similar to a deluge valve). In this way, the system is essentially converted from a dry system into a wet system. The intent is to reduce the undesirable time delay of water delivery to sprinklers that is inherent in dry systems. Prior to fire detection, if the sprinkler operates, or the piping system develops a leak, loss of air pressure in the piping will activate a trouble alarm. In this case, the pre-action valve will not open due to loss of supervisory pressure, and water will not enter the piping.
840:
commercial sprinkler system is designed to protect the structure and the occupants from a fire. Most residential sprinkler systems are primarily designed to control a fire for a sufficient time to allow for the safe escape of the building occupants. While these systems will often also protect the structure from major fire damage, this is a secondary consideration. In residential structures, sprinklers are often omitted from closets, bathrooms, balconies, garages and attics because a fire in these areas would not usually impact the occupant's escape route.
366:. The glass bulb or link hold in place a "pip cap" which acts as a plug to prevent water from flowing, unless the ambient temperature around the sprinkler reaches the design activation temperature of the individual sprinkler head. In a standard wet-pipe sprinkler system, each sprinkler activates independently when the predetermined heat level is reached. Thus, only sprinklers near the heat of the fire will operate, normally just one or two. This maximizes water pressure over the point of fire origin, and minimizes water damage to the building. 131: 342:, a design guide for fire safety in schools, that most new schools, except for a few low risk schools, should be constructed with sprinkler protection. In 2011, Wales became the first country in the world where sprinklers are compulsory in all new homes. The law applies to newly built houses and blocks of flats, as well as care homes and university halls of residence. In Scotland, all new schools are sprinklered, as are new care homes, sheltered housing and high rise flats. 416: 771: 2326: 487: 824:
over the 1,500-square-foot (140 m) design area. Another example would be a manufacturing facility classified as ordinary hazard group 2 where a typical design area would be 1,500 square feet (140 m) and the design density would be 0.2 US gallons per minute (0.76 L/min) per 1 square foot (0.093 m) or a minimum of 300 US gallons per minute (1,100 L/min) applied over the 1,500-square-foot (140 m) design area.
25: 864:(NFPA), fires in hotels with sprinklers averaged 78% less damage than fires in hotels without them (1983–1987). The NFPA says the average loss per fire in buildings with sprinklers was $ 2,300, compared to an average loss of $ 10,300 in unsprinklered buildings. However, in a purely economic comparison, this is not a complete picture; the total costs of fitting, and the costs arising from non-fire triggered release must be factored. 301:. This law requires that any hotel, meeting hall, or similar institution that receives federal funds (i.e. for overnight stay, or a conference, etc.), must meet fire and other safety requirements. The most visible of these conditions is the implementation of sprinklers. As more and more hotels and other public accommodations upgraded their facilities to enable business with government visitors, this type of construction became the 383: 2338: 228:, including, but not limited to newly constructed "hospitals, schools, hotels and other public buildings", subject to the local building codes and enforcement. However, outside of the US and Canada, sprinklers have rarely been mandated by building codes for normal hazard occupancies which do not have large numbers of occupants (e.g. factories, process lines, retail outlets, petrol stations, etc.) 531:"Deluge" systems are systems in which all sprinklers connected to the water piping system are open, in that the heat sensing operating element is removed. These systems are used for special hazards where rapid fire spread is a concern, as they provide a simultaneous application of water over the entire hazard. 224:"Until the 1940s, sprinklers were installed almost exclusively for the protection of commercial buildings, whose owners were generally able to recoup their expenses with savings in insurance costs. Over the years, fire sprinklers have become mandatory safety equipment" in some parts of North America, in certain 445:
the time that sprinkler is activated is limited to a maximum of 60 seconds. In industry practice, this is known as the "Maximum Time of Water Delivery". The maximum time of water delivery may be required to be reduced, depending on the hazard classification of the area protected by the sprinkler system.
631:
of the "Outside Screw and Yoke" (OS&Y) type, sometimes called "rising stem" valves; or butterfly valves. The position (open or closed) of these valves can be determined visually. Alarm sensors may be attached to monitor the settings of these valves, which are critical to overall building safety.
573:
Double interlock systems require that both activation of a heat or smoke detector, and an automatic sprinkler operation take place prior to the "action" of water introduction into the system's piping. Activation of either the fire detectors alone, or sprinklers alone, without the concurrent operation
477:
Increased fire response time: Because the piping is empty at the time the sprinkler operates, there is an inherent time delay in delivering water to the sprinklers which have operated while the water travels from the riser to the sprinkler, partially filling the piping in the process. A maximum of 60
423:
Dry pipe systems are the second most common sprinkler system type. Dry pipe systems are installed in spaces in which the ambient temperature may be cold enough to freeze the water in a wet pipe system, which would make the system inoperable. Dry pipe systems are most often used in unheated buildings,
369:
A sprinkler activation will usually do less water damage than a fire department hose stream (which provide approximately 900 litres/min (250 US gallons/min). A typical sprinkler used for industrial manufacturing occupancies discharges about 75–150 litres/min (20–40 US gallons/min). However, a typical
308:
If building codes do not explicitly mandate the use of fire sprinklers, the code often makes it highly advantageous to install them as an optional system. Most US building codes allow for less-expensive construction materials, larger floor area limitations, longer egress paths, and fewer requirements
839:
Sprinkler systems in residential structures are becoming more common, as the cost of such systems becomes more practical and the benefits become more obvious. Residential sprinkler systems usually fall under a residential classification separate from the commercial classifications mentioned above. A
823:
For example, in an office building classified as light hazard, a typical design area would be 1,500 square feet (140 m) and the design density would be 0.1 US gallons per minute (0.38 L/min) per 1 square foot (0.093 m) or a minimum of 150 US gallons per minute (570 L/min) applied
814:
Control mode sprinkler systems are designed using an area and density approach. The building use and contents are analyzed to determine the level of fire hazard. The hazard is classified as light hazard, ordinary hazard group 1, ordinary hazard group 2, extra hazard group 1, or extra hazard group 2.
614:
Water mist systems are used for special hazards applications. This type of system is typically used where water damage may be a concern, or where water supplies are limited. NFPA 750 defines water mist as a water spray with a droplet size of "less than 1000 microns at the minimum operation pressure
538:
Because the heat sensing elements normally present in automatic sprinklers have been removed (resulting in open sprinkler heads), the deluge valve is opened via a signal from the fire alarm system which utilizes fire detectors. The type of fire alarm initiating device is selected mainly based on the
473:
Lower design flexibility: Regulatory requirements limit the maximum permitted size (i.e. 750 gallons) of individual dry-pipe systems, unless additional components and design efforts are provided to limit the time from sprinkler activation to water discharge to under 60 seconds. These limitations may
444:
across the dry pipe valve changes, allowing water to enter the piping system. Water flow from sprinklers, needed to control the fire, is delayed until the air is vented from the sprinklers. In regions using NFPA 13 regulations, the time it takes water to reach the hydraulically remote sprinkler from
406:
While such systems were once common in cold areas, after several fires which were not controlled because of sprinkler systems filled with too high a percentage of antifreeze, the regulatory authority in the United States effectively banned new antifreeze installations. A sunset date of 2022 applies
373:
In addition, a sprinkler will usually activate within one to four minutes of the fire's start, whereas it typically takes at least five minutes for a fire department to register an alarm and drive to the fire site, and an additional ten minutes to set up equipment and apply hose streams to the fire.
161:
Fire sprinkler systems are extensively used worldwide, with over 40 million sprinkler heads fitted each year. Fire sprinkler systems are generally designed as a life saving system, but are not necessarily designed to protect the building. Of buildings completely protected by fire sprinkler systems,
618:
In operation, water mist systems can operate with the same functionality as deluge, wet pipe, dry pipe, or pre-action systems. The difference is that a water mist system uses a compressed gas as an atomizing medium, which is pumped through the sprinkler pipe. Instead of compressed gas, some systems
521:
can be used as a permanent source of nitrogen gas, which is beneficial because dry pipe sprinkler systems require an uninterrupted supply of supervisory gas. These additional precautions can increase the up-front cost of the system, but will help prevent system failure, increased maintenance costs,
504:
available in the compressed air in the piping, increases internal pipe corrosion, eventually leading to pin-hole leaks or other piping failures. The internal corrosion rate in wet pipe systems (in which the piping is constantly full of water) is much lower, as the amount of oxygen available for the
431:
Water is not present in the piping until the system operates; instead, the piping is filled with dry air at a pressure below the water supply pressure. To prevent the larger water supply pressure from prematurely forcing water into the piping, the design of the dry pipe valve (a specialized type of
244:
Sprinklers have been in use in the United States since 1874, and were installed into factory applications where fires at the turn of the century had often catastrophic in terms of both human and property losses. In the US, sprinklers are today required in all new high rise and underground buildings
179:
designed a sprinkler system in the 15th century. Leonardo automated his patron's kitchen with a super-oven and a system of conveyor belts. In a comedy of errors, everything went wrong during a huge banquet, and a fire broke out. "The sprinkler system worked all too well, causing a flood that washed
395:
By a wide margin, wet pipe sprinkler systems are installed more often than all other types of fire sprinkler systems. They also are the most reliable, because they are simple, with the only operating components being the automatic sprinklers and (commonly, but not always) the automatic alarm check
345:
In the UK, since the 1990s sprinklers have gained recognition within the Building Regulations (England and Wales) and Scottish Building Standards and under certain circumstances, the presence of sprinkler systems is deemed to provide a form of alternative compliance to some parts of the codes. For
856:
water supplies ("fire flows") are not available. Nationwide in the United States, one and two-family homes generally do not require fire sprinkler systems, although the overwhelming loss of life due to fires occurs in these spaces. Residential sprinkler systems are inexpensive (about the same per
321:
In Norway as of July 2010, all new housing of more than two storeys, all new hotels, care homes, and hospitals must be sprinklered. Other Nordic countries require or soon will require sprinklers in new care homes, and in Finland as of 2010 a third of care homes were retrofitted with sprinklers. A
312:
In 2011, Pennsylvania and California became the first US states to require sprinkler systems in all new residential construction. However, Pennsylvania repealed the law later that same year. Many municipalities now require residential sprinklers, even if they are not required at the state level.
827:
After the design area and density have been determined, calculations are performed to prove that the system can deliver the required amount of water over the required design area. These calculations account for all of the pressure that is lost or gained between the water supply source and the
569:
The operation of single interlock systems are similar to wet systems except that these systems require that a "preceding" fire detection event, typically the activation of a heat or smoke detector takes place prior to the "action" of water introduction into the system's piping by opening the
462:
Increased complexity: Dry pipe systems require additional control equipment and air pressure supply components, which increases system complexity. This puts a premium on proper maintenance, as this increase in system complexity results in an inherently less-reliable overall system (i.e. more
534:
Water is not present in the piping until the system operates. Because the sprinkler orifices are open, the piping is at atmospheric pressure. To prevent the water supply pressure from forcing water into the piping, a "deluge valve" (a mechanically latched valve) is used in the water supply
309:
for fire-rated construction in structures which are protected by fire sprinklers. Consequently, the total building cost is often decreased by installing a sprinkler system and saving money in the other aspects of the project, as compared to building a non-sprinklered structure.
848:
In 2008, the installed costs of sprinkler systems ranged from US$ 0.31 – $ 3.66 per square foot, depending on type and location. Residential systems, installed at the time of initial home construction and utilizing municipal water supplies, average about US$ 0.35/square foot.
615:
of the discharge nozzle". The droplet size can be controlled by adjusting the discharge pressure through a nozzle of a fixed orifice size. The fire suppression mechanisms provided by water mist systems include cooling, local flame oxygen reduction, and radiation blocking.
439:
When one or more of the automatic sprinkler heads is triggered, it opens, allowing the air in the piping to vent from that sprinkler. Each sprinkler operates independently, as its temperature rises above its triggering threshold. As the air pressure in the piping drops, the
574:
of the other will not allow water to enter the piping. Because water does not enter the piping until a sprinkler operates, double interlock systems are considered as dry systems in terms of water delivery times, and similarly require a larger design area.
551:). The initiation device signals the fire alarm panel, which in turn signals the deluge valve to open. Activation can also be via an electric or pneumatic fire alarm pull station which signals the fire alarm panel to signal the deluge valve to open. 819:
standard. The design area is a theoretical area of the building representing the worst case area where a fire could burn. The design density is a measurement of how much water per square foot of floor area should be applied to the design area.
499:
potential: Following operation or testing, dry-pipe sprinkler system piping should be drained, but residual water collects in piping low spots, and moisture is also retained in the atmosphere within the piping. This moisture, coupled with the
293:
or NFPA. NFPA sets the standards for technical aspects of sprinklers installed in the USA. Building codes, which specify which buildings require sprinklers are generally left to local jurisdictions. However, there are some exceptions:
231:
Sprinklers are now commonly installed in non-industrial buildings, including schools and residential premises. This is largely as a result of lobbying by the National Fire Sprinkler Network, the European Fire Sprinkler Network, and the
875:
or where industrial fire brigade members or employees were killed during fire suppression operations." Elsewhere it has stated, "NFPA has no record of a multiple fatality in a fully sprinklered building where the system operated."
794:
of the fire to prevent building structure collapse, and pre-wet the surrounding combustibles to prevent fire spread. The fire is not extinguished until the burning combustibles are exhausted or manual extinguishment is effected by
619:
use a high-pressure pump to pressurize the water so it atomizes as it exits the sprinkler nozzle. Systems can be applied using local application method or total flooding method, similar to Clean Agent Fire Protection Systems.
346:
example, the presence of a sprinkler system will usually permit doubling of compartment sizes and increases in travel distances (to fire exits) as well as allowing a reduction in the fire rating of internal compartment walls.
276:, usually require sprinklers either under local building codes, as a condition of receiving State and Federal funding, or as a requirement to obtain certification (essential for institutions who wish to train medical staff). 436:) results in a greater force on top of the check valve clapper by the use of a larger valve clapper area exposed to the piping air pressure, as compared to the higher water pressure but smaller clapper surface area. 337:
Renewed interest in and support for sprinkler systems in the UK has resulted in sprinkler systems being more widely installed. In schools, for example, the government has issued recommendations through
221:'s design and in 1881 patented the automatic sprinkler that bears his name. He continued to improve the device and in 1890 invented the glass disc sprinkler, essentially the same as that in use today. 452:
and other water-sensitive areas. This perceived benefit is due to a fear that wet system piping may slowly leak water without attracting notice, while dry pipe systems should not fail in this manner.
459:
If the sprinklers share the same standpipe system as the standpipe system which supplies fire hoses, then the water supply to the fire hoses would be severely reduced or even curtailed altogether.
470:
Higher installation and maintenance costs: The added complexity impacts the overall dry-pipe installation cost, and increases maintenance expenditure primarily due to added service labor costs.
201:(c. 95,000 litres) fed by a 10-inch (250 mm) water main which branched to all parts of the theatre. A series of smaller pipes fed from the distribution pipe were pierced with a series of 1076: 260:
to reduce potential property losses or business interruption. US building codes for places of assembly (generally over 100 persons) and places with overnight sleeping accommodation such as
474:
increase the number of individual sprinkler zones (i.e. served from a single riser) that must be provided in the building, and impact the ability of an owner to make system additions.
984: 833: 867:
The NFPA states that it "has no record of a fire killing more than two people in a completely sprinklered building where a sprinkler system was properly operating, except in an
1228: 1412: 370:
Early Suppression Fast Response (ESFR) sprinkler at a pressure of 50 psi (340 kPa) will discharge approximately 380 litres per minute (100 US gal/min).
158:
are connected. Although initially used only in factories and large commercial buildings, systems for homes and small buildings are now available at a cost-effective price.
852:
Systems can be installed during initial construction, or retrofitted. Some communities have laws requiring residential sprinkler systems, especially where large municipal
2173: 1162: 586:
concentrate, resulting in a foam spray from the sprinkler. These systems are usually used with special hazards occupancies associated with high challenge fires, such as
857:
square foot as carpeting or floor tiling), but require larger water supply piping than is normally installed in homes, so retrofitting is usually cost prohibitive.
1206: 1130: 326:
in the Netherlands on 27 October 2005 killed 11 detainees, and led to the retrofitting of sprinklers in all similarly-designed prisons in the Netherlands. A
407:
to older antifreeze systems in the US. This regulatory action has greatly increased costs and reduced options for cold weather tolerant sprinkler systems.
791: 428:. In regions using NFPA regulations, wet pipe systems cannot be installed unless the range of ambient temperatures remains above 40 °F (4 °C). 1968: 478:
seconds is normally allowed by regulatory requirements from the time a single sprinkler opens until water is discharged onto the fire. This delay in
1072: 1180: 138:
will spray water into the room if sufficient heat reaches the bulb and causes it to shatter. Sprinkler heads operate individually. Note the
2161: 233: 980: 1776: 811:) sprinklers, are intended to result in a severe sudden reduction of the heat release rate of the fire, prior to manual intervention. 1466: 154:
method, consisting of a water supply system providing adequate pressure and flowrate to a water distribution piping system, to which
957: 563:
with rare art works, manuscripts, or books; and data centers, for protection of computer equipment from accidental water discharge.
559:
Pre-action sprinkler systems are specialized for use in locations where accidental activation is especially undesirable, such as in
424:
in parking garages, in outside canopies attached to heated buildings (within which a wet pipe system would also be provided), or in
89: 1494: 61: 2140: 913: 298: 42: 1154: 197:, and was covered by patent No. 3606 dated the same year. The apparatus consisted of a cylindrical airtight reservoir of 400 186:
created the first successful automated sprinkler system in 1723. He used gunpowder to release a tank of extinguishing fluid.
68: 362:
Each closed-head sprinkler is held closed by either a heat-sensitive glass bulb or a two-part metal link held together with
2185: 2179: 1083: 861: 816: 290: 1008:"The+sprinkler+system+worked+all+too+well,+causing+a+flood+that+washed+away+all+the+food+and+a+good+part+of+the+kitchen." 1384: 1249: 815:
After determining the hazard classification, a design area and density can be determined by referencing tables in the 13
334:. Most European countries also require sprinklers in shopping centers, in large warehouses, and in high-rise buildings. 1681: 1100: 75: 1202: 2056: 1126: 1018: 582:
A foam water fire sprinkler system is a special application system, discharging a mixture of water and low expansion
194: 108: 2341: 57: 2369: 2364: 1817: 1505: 46: 121:
This article is about the complete fire protection system. For the device that actually discharges water, see
2167: 2124: 1796: 1459: 1348: 1271: 2285: 2238: 2076: 1312: 448:
Some property owners and building occupants may view dry pipe sprinklers as advantageous for protection of
2109: 2041: 1858: 1691: 908: 331: 1676: 1616: 1176: 327: 2394: 2374: 2191: 2026: 1686: 898: 354: 190: 2329: 2135: 2051: 2031: 2008: 1771: 1536: 1452: 829: 479: 82: 1978: 1943: 1791: 1741: 918: 35: 1373:"Home Fire Sprinkler Cost Assessment", published 2008 by the Fire Protection Research Foundation 374:
This additional time can result in a much larger fire, requiring much more water to extinguish.
2119: 1998: 1973: 1963: 1671: 1631: 893: 162:
if a fire did initiate, it was controlled by the fire sprinklers alone in 96% of these cases.
151: 832:
who seeks senior level certification from engineering certification organizations such as the
2306: 2280: 2233: 1848: 1716: 627:
Major control and isolation valves in traditional fire sprinkler systems are typically large
879:
The world's largest fire sprinkler manufacturer is the Fire Protection Products division of
566:
There are two main sub-types of pre-action systems: single interlock, and double interlock.
2003: 1863: 1571: 464: 245:
generally 75 feet (23 m) above or below fire department access, where the ability of
8: 2379: 2046: 1953: 953: 330:
on 11 April 1996 which killed 17 people led to sprinklers being retrofitted in all major
1007: 1833: 1761: 1726: 1721: 1576: 880: 518: 214: 130: 2384: 2259: 2254: 2249: 2145: 2036: 2018: 1908: 1746: 1656: 1641: 1014: 928: 396:
valve. An automatic water supply provides water under pressure to the system piping.
257: 218: 176: 403:
chemical, for use where pipes cannot reliably be kept above 40 °F (4 °C).
2243: 1581: 587: 449: 323: 2389: 1938: 1873: 1812: 1781: 1756: 1706: 1701: 1515: 1475: 1080: 903: 510: 183: 2104: 2081: 2066: 1928: 1868: 1838: 1807: 1751: 1711: 1646: 1636: 1531: 1241: 1104: 548: 540: 490:
Dry pipe sprinkler system supply main with corrosion debris caused by oxidation
171: 155: 135: 122: 2358: 2311: 2301: 2099: 2071: 1988: 1606: 1596: 1566: 1510: 1059: 1046: 544: 363: 305:
industry norm – even when not directly mandated by any local building codes.
253: 189:
The world's first modern recognizable sprinkler system was installed in the
2228: 2114: 1993: 1983: 1918: 1883: 1843: 1802: 1766: 1556: 1551: 1521: 923: 853: 425: 265: 415: 1948: 1903: 1893: 1786: 1731: 1696: 1591: 796: 433: 246: 770: 211:-inch (13 mm) holes which would pour water in the event of a fire. 2208: 2061: 1561: 1546: 1526: 872: 628: 486: 400: 1385:"A Brief Introduction to Sprinkler Systems for Life Safety Code Users" 535:
connection. It is a non-resetting valve, and stays open once tripped.
505:
corrosion process is more limited. Corrosion can be combated by using
482:
results in a larger fire prior to control, increasing property damage.
2130: 1958: 1923: 1913: 1898: 1878: 1853: 1626: 1621: 1586: 1541: 1489: 1313:"Fundamental Corrosion Control Strategies for Fire Sprinkler Systems" 933: 868: 496: 269: 225: 24: 2223: 1933: 1888: 1611: 1601: 1500: 514: 441: 302: 273: 198: 1444: 382: 834:
National Institute for Certification in Engineering Technologies
455:
Disadvantages of using dry pipe fire sprinkler systems include:
358:
A sign warns hotel guests not to hang items from fire sprinklers
591: 560: 506: 501: 2264: 2218: 603: 261: 2213: 2174:
National Council of Examiners for Engineering and Surveying
1036:"History of Sprinkler Systems". Associated Fire Protection. 808: 774:
Sprinkler glass bulbs with different operating temperatures
583: 513:
pipe which are less susceptible to corrosion, or by using
289:
The primary fire code writing organization is the private
522:
and premature need for system replacement in the future.
1242:"Fire sprinklers compulsory for all new homes in Wales" 1439: 1349:"Guide to OS&Y Valves for Fire Protection Systems" 1177:"Pennsylvania repeals automatic sprinkler requirement" 297:
In 1990 the US passed PL-101-391, better known as the
249:
to provide adequate hose streams to fires is limited.
1098: 1013:. New York, New York: Dell Publishing. p. 79. 180:away all the food and a good part of the kitchen." 49:. Unsourced material may be challenged and removed. 1413:"NFPA Journal – The Case for Home Fire Sprinklers" 1969:Penetrant (mechanical, electrical, or structural) 1272:"The End of Antifreeze in Fire Sprinkler Systems" 399:Wet systems have optionally been charged with an 322:fire in an illegal immigrant detention center at 2356: 1355:. Quick Response Fire Supply, LLC. 16 March 2022 193:in the United Kingdom in 1812 by its architect, 1227:Department for Children, Schools and Families, 1155:"Builders Smokin' Mad Over New Sprinkler Rules" 517:gas to pressurize the system, rather than air. 252:Sprinklers may be required to be installed by 1460: 234:British Automatic Fire Sprinkler Association 1143:National Fire Protection Association (NFPA) 1777:Hypoxic air technology for fire prevention 1467: 1453: 1274:. Fire Safety Advice Centre. 16 March 2018 843: 760:and the respective operating temperature. 2162:Fire Equipment Manufacturers' Association 1094: 1092: 778:Sprinkler systems are intended to either 756:This chart from the fire safety standards 109:Learn how and when to remove this message 1495:Boiling liquid expanding vapor explosion 1032: 1030: 769: 485: 419:Garage sprinkler system in New York City 414: 381: 353: 129: 2141:Listing and approval use and compliance 1152: 1146: 914:Listing and approval use and compliance 790:sprinklers are intended to control the 299:Hotel and Motel Fire Safety Act of 1990 2357: 1292:NFPA 13 2007 ed. Sections 7-2 and A7-2 1165:from the original on 2 September 2017. 1089: 2186:Society of Fire Protection Engineers 1448: 1382: 1027: 386:Fire sprinkler control valve assembly 2337: 2180:National Fire Protection Association 1440:National Fire Protection Association 1392:National Fire Protection Association 1341: 1317:Society of Fire Protection Engineers 1310: 1133:from the original on 22 January 2015 1005: 978: 960:from the original on 16 January 2013 862:National Fire Protection Association 817:National Fire Protection Association 291:National Fire Protection Association 47:adding citations to reliable sources 18: 1474: 1010:How to Think Like Leonardo da Vinci 972: 467:) as compared to a wet pipe system. 13: 1682:Condensed aerosol fire suppression 1252:from the original on 5 August 2011 1153:Wotapka, Dawn (22 December 2010). 987:from the original on 12 March 2016 14: 2406: 2057:Fire alarm notification appliance 1433: 1209:from the original on 10 July 2015 1203:"Sprinkler requirements by state" 1183:from the original on 11 July 2015 2336: 2325: 2324: 1655: 1301:NFPA 13 2010 ed. Table 7.2.3.6.1 758:indicates the color of the bulb 284: 23: 1818:Vehicle fire suppression system 1506:Combustibility and flammability 1405: 1376: 1367: 1332: 1323: 1304: 1295: 1286: 1264: 1234: 1221: 1195: 1169: 981:"US Experience with Sprinklers" 979:Hall, John R. Jr. (June 2013). 805:Early Suppression Fast Response 747: 730: 717: 704: 693: 680: 667: 539:hazard (e.g. pilot sprinklers, 34:needs additional citations for 1119: 1065: 1052: 1039: 999: 946: 597: 279: 1: 2168:Institution of Fire Engineers 2125:Fire Safety Evaluation System 1797:Personal protective equipment 956:. Fire Safety Advice Centre. 940: 609: 577: 554: 2239:GHS precautionary statements 2077:Manual fire alarm activation 1353:QRFS - Thoughts on Fire Blog 954:"Industrial Fire sprinklers" 349: 140:red liquid in the glass bulb 7: 2110:Fire protection engineering 2042:Explosive gas leak detector 1859:Electromagnetic door holder 1692:External water spray system 1071:Casey Cavanaugh Grant, PE " 909:Fire protection engineering 886: 410: 390: 256:, or may be recommended by 139: 10: 2411: 2286:Harry C. Bigglestone Award 1677:Automatic fire suppression 1617:K-factor (fire protection) 803:sprinklers, also known as 328:fire at Düsseldorf Airport 169: 165: 120: 2320: 2294: 2273: 2201: 2192:Underwriters Laboratories 2154: 2090: 2027:Aspirating smoke detector 2017: 1826: 1687:Detonation flame arrester 1664: 1653: 1482: 1383:Dubay, Christian (2006). 1311:Kirn, Lucas (June 2016). 1099:Merit Sprinkler Company. 1006:Gelb, Michael J. (2000). 899:Architectural engineering 754: 645: 642: 635: 622: 526: 316: 191:Theatre Royal, Drury Lane 2136:Kitchen exhaust cleaning 2052:Fire alarm control panel 2032:Carbon monoxide detector 2009:Standpipe (firefighting) 1772:Gaseous fire suppression 1537:Enthalpy of vaporization 1079:28 December 2007 at the 377: 239: 1979:Pressurisation ductwork 1944:Firewall (construction) 1792:Passive fire protection 1742:Fire suppression system 1159:The Wall Street Journal 919:Passive fire protection 844:Costs and effectiveness 58:"Fire sprinkler system" 2370:Active fire protection 2365:Firefighting equipment 2155:Industry organizations 2120:Fire-resistance rating 1999:Smoke exhaust ductwork 1974:Penetration (firestop) 1964:Packing (firestopping) 1672:Active fire protection 1632:Spontaneous combustion 1231:, accessed 1 June 2021 894:Active fire protection 775: 590:, such as in aircraft 491: 420: 387: 359: 152:active fire protection 143: 16:Fire protection method 2307:Template:Firefighting 2281:Arthur B. Guise Medal 2234:GHS hazard statements 1737:Fire sprinkler system 1717:Fire-retardant fabric 1229:Building Bulletin 100 773: 489: 465:single failure points 442:pressure differential 418: 385: 357: 340:Building Bulletin 100 148:fire sprinkler system 133: 2091:Professions, trades, 2004:Smokeproof enclosure 1864:Electromagnetic lock 1572:Flammability diagram 1483:Fundamental concepts 1248:. 16 February 2011. 450:valuable collections 426:refrigerated coolers 43:improve this article 2047:Fire alarm call box 1954:Heat and smoke vent 1127:"Hotels and motels" 1101:"Sprinkler History" 1060:U.S. patent 431,971 1047:U.S. patent 248,828 606:) and fire spread. 519:Nitrogen generators 258:insurance companies 2019:Fire alarm systems 1834:Annulus (firestop) 1762:Flashback arrestor 1727:Fire-safe polymers 1722:Fire retardant gel 1577:Flammability limit 881:Tyco International 776: 492: 421: 388: 360: 215:Frederick Grinnell 144: 134:A glass bulb type 2352: 2351: 2260:Safety data sheet 2255:List of S-phrases 2250:List of R-phrases 2146:Sprinkler fitting 2037:Circuit integrity 1909:Fire extinguisher 1747:Firefighting foam 1642:Thermal radiation 1107:on 11 August 2006 1073:The Birth of NFPA 929:Sprinkler fitting 860:According to the 792:heat release rate 765: 764: 588:flammable liquids 219:Henry S. Parmalee 177:Leonardo da Vinci 119: 118: 111: 93: 2402: 2395:Fire suppression 2375:Safety equipment 2340: 2339: 2328: 2327: 2244:Life Safety Code 1849:Compartmentation 1659: 1582:Flammable liquid 1469: 1462: 1455: 1446: 1445: 1428: 1427: 1425: 1423: 1409: 1403: 1402: 1400: 1398: 1389: 1380: 1374: 1371: 1365: 1364: 1362: 1360: 1345: 1339: 1336: 1330: 1327: 1321: 1320: 1308: 1302: 1299: 1293: 1290: 1284: 1283: 1281: 1279: 1268: 1262: 1261: 1259: 1257: 1238: 1232: 1225: 1219: 1218: 1216: 1214: 1199: 1193: 1192: 1190: 1188: 1173: 1167: 1166: 1150: 1144: 1142: 1140: 1138: 1123: 1117: 1116: 1114: 1112: 1103:. Archived from 1096: 1087: 1069: 1063: 1062: 1056: 1050: 1049: 1043: 1037: 1034: 1025: 1024: 1003: 997: 996: 994: 992: 976: 970: 969: 967: 965: 950: 801:Suppression mode 750: 733: 720: 707: 683: 670: 646:Color of liquid 640: 639: 480:fire suppression 324:Schiphol Airport 210: 209: 205: 195:William Congreve 114: 107: 103: 100: 94: 92: 51: 27: 19: 2410: 2409: 2405: 2404: 2403: 2401: 2400: 2399: 2355: 2354: 2353: 2348: 2316: 2290: 2269: 2197: 2150: 2092: 2086: 2013: 1939:Firestop pillow 1874:Emergency light 1827:Building design 1822: 1813:Tank blanketing 1782:Inerting system 1757:Flame retardant 1707:Fire protection 1702:Fire prevention 1660: 1651: 1516:Dangerous goods 1478: 1476:Fire protection 1473: 1436: 1431: 1421: 1419: 1411: 1410: 1406: 1396: 1394: 1387: 1381: 1377: 1372: 1368: 1358: 1356: 1347: 1346: 1342: 1337: 1333: 1328: 1324: 1309: 1305: 1300: 1296: 1291: 1287: 1277: 1275: 1270: 1269: 1265: 1255: 1253: 1240: 1239: 1235: 1226: 1222: 1212: 1210: 1201: 1200: 1196: 1186: 1184: 1175: 1174: 1170: 1151: 1147: 1136: 1134: 1125: 1124: 1120: 1110: 1108: 1097: 1090: 1081:Wayback Machine 1070: 1066: 1058: 1057: 1053: 1045: 1044: 1040: 1035: 1028: 1021: 1004: 1000: 990: 988: 977: 973: 963: 961: 952: 951: 947: 943: 938: 904:Fire protection 889: 846: 782:the fire or to 767: 759: 757: 748: 744: 739: 731: 718: 705: 681: 668: 638: 625: 612: 600: 580: 557: 549:flame detectors 541:smoke detectors 529: 511:stainless steel 413: 393: 380: 352: 332:German airports 319: 287: 282: 242: 207: 203: 202: 184:Ambrose Godfrey 174: 168: 156:fire sprinklers 126: 115: 104: 98: 95: 52: 50: 40: 28: 17: 12: 11: 5: 2408: 2398: 2397: 2392: 2387: 2382: 2377: 2372: 2367: 2350: 2349: 2347: 2346: 2334: 2321: 2318: 2317: 2315: 2314: 2309: 2304: 2298: 2296: 2292: 2291: 2289: 2288: 2283: 2277: 2275: 2271: 2270: 2268: 2267: 2262: 2257: 2252: 2247: 2241: 2236: 2231: 2226: 2221: 2216: 2211: 2205: 2203: 2199: 2198: 2196: 2195: 2189: 2183: 2177: 2171: 2165: 2158: 2156: 2152: 2151: 2149: 2148: 2143: 2138: 2133: 2128: 2122: 2117: 2112: 2107: 2105:Fire insurance 2102: 2096: 2094: 2088: 2087: 2085: 2084: 2082:Smoke detector 2079: 2074: 2069: 2067:Flame detector 2064: 2059: 2054: 2049: 2044: 2039: 2034: 2029: 2023: 2021: 2015: 2014: 2012: 2011: 2006: 2001: 1996: 1991: 1986: 1981: 1976: 1971: 1966: 1961: 1956: 1951: 1946: 1941: 1936: 1931: 1929:Fire sprinkler 1926: 1921: 1916: 1911: 1906: 1901: 1896: 1891: 1886: 1881: 1876: 1871: 1869:Emergency exit 1866: 1861: 1856: 1851: 1846: 1841: 1839:Area of refuge 1836: 1830: 1828: 1824: 1823: 1821: 1820: 1815: 1810: 1808:Spark arrestor 1805: 1800: 1794: 1789: 1784: 1779: 1774: 1769: 1764: 1759: 1754: 1752:Flame arrester 1749: 1744: 1739: 1734: 1729: 1724: 1719: 1714: 1712:Fire retardant 1709: 1704: 1699: 1694: 1689: 1684: 1679: 1674: 1668: 1666: 1662: 1661: 1654: 1652: 1650: 1649: 1647:Water pressure 1644: 1639: 1637:Structure fire 1634: 1629: 1624: 1619: 1614: 1609: 1604: 1599: 1594: 1589: 1584: 1579: 1574: 1569: 1564: 1559: 1554: 1549: 1544: 1539: 1534: 1532:Dust explosion 1529: 1524: 1519: 1513: 1508: 1503: 1498: 1492: 1486: 1484: 1480: 1479: 1472: 1471: 1464: 1457: 1449: 1443: 1442: 1435: 1434:External links 1432: 1430: 1429: 1404: 1375: 1366: 1340: 1338:NFPA 750,1.2.1 1331: 1322: 1303: 1294: 1285: 1263: 1233: 1220: 1194: 1168: 1145: 1118: 1088: 1064: 1051: 1038: 1026: 1019: 998: 971: 944: 942: 939: 937: 936: 931: 926: 921: 916: 911: 906: 901: 896: 890: 888: 885: 845: 842: 763: 762: 752: 751: 746: 741: 735: 734: 729: 726: 722: 721: 716: 713: 709: 708: 703: 700: 696: 695: 692: 689: 685: 684: 679: 676: 672: 671: 666: 663: 659: 658: 655: 651: 650: 644: 637: 634: 624: 621: 611: 608: 599: 596: 579: 576: 556: 553: 545:heat detectors 528: 525: 524: 523: 484: 483: 475: 471: 468: 460: 412: 409: 392: 389: 379: 376: 351: 348: 318: 315: 286: 283: 281: 278: 254:building codes 241: 238: 172:Fire sprinkler 167: 164: 136:sprinkler head 123:Fire sprinkler 117: 116: 31: 29: 22: 15: 9: 6: 4: 3: 2: 2407: 2396: 2393: 2391: 2388: 2386: 2383: 2381: 2378: 2376: 2373: 2371: 2368: 2366: 2363: 2362: 2360: 2345: 2344: 2335: 2333: 2332: 2323: 2322: 2319: 2313: 2312:Template:HVAC 2310: 2308: 2305: 2303: 2302:Template:Fire 2300: 2299: 2297: 2293: 2287: 2284: 2282: 2279: 2278: 2276: 2272: 2266: 2263: 2261: 2258: 2256: 2253: 2251: 2248: 2245: 2242: 2240: 2237: 2235: 2232: 2230: 2227: 2225: 2222: 2220: 2217: 2215: 2212: 2210: 2207: 2206: 2204: 2200: 2193: 2190: 2187: 2184: 2181: 2178: 2175: 2172: 2169: 2166: 2163: 2160: 2159: 2157: 2153: 2147: 2144: 2142: 2139: 2137: 2134: 2132: 2129: 2126: 2123: 2121: 2118: 2116: 2113: 2111: 2108: 2106: 2103: 2101: 2100:Duct cleaning 2098: 2097: 2095: 2089: 2083: 2080: 2078: 2075: 2073: 2072:Heat detector 2070: 2068: 2065: 2063: 2060: 2058: 2055: 2053: 2050: 2048: 2045: 2043: 2040: 2038: 2035: 2033: 2030: 2028: 2025: 2024: 2022: 2020: 2016: 2010: 2007: 2005: 2002: 2000: 1997: 1995: 1992: 1990: 1989:Smoke control 1987: 1985: 1982: 1980: 1977: 1975: 1972: 1970: 1967: 1965: 1962: 1960: 1957: 1955: 1952: 1950: 1947: 1945: 1942: 1940: 1937: 1935: 1932: 1930: 1927: 1925: 1922: 1920: 1917: 1915: 1912: 1910: 1907: 1905: 1902: 1900: 1897: 1895: 1892: 1890: 1887: 1885: 1882: 1880: 1877: 1875: 1872: 1870: 1867: 1865: 1862: 1860: 1857: 1855: 1852: 1850: 1847: 1845: 1842: 1840: 1837: 1835: 1832: 1831: 1829: 1825: 1819: 1816: 1814: 1811: 1809: 1806: 1804: 1801: 1798: 1795: 1793: 1790: 1788: 1785: 1783: 1780: 1778: 1775: 1773: 1770: 1768: 1765: 1763: 1760: 1758: 1755: 1753: 1750: 1748: 1745: 1743: 1740: 1738: 1735: 1733: 1730: 1728: 1725: 1723: 1720: 1718: 1715: 1713: 1710: 1708: 1705: 1703: 1700: 1698: 1695: 1693: 1690: 1688: 1685: 1683: 1680: 1678: 1675: 1673: 1670: 1669: 1667: 1663: 1658: 1648: 1645: 1643: 1640: 1638: 1635: 1633: 1630: 1628: 1625: 1623: 1620: 1618: 1615: 1613: 1610: 1608: 1607:Heat transfer 1605: 1603: 1600: 1598: 1597:Friction loss 1595: 1593: 1590: 1588: 1585: 1583: 1580: 1578: 1575: 1573: 1570: 1568: 1567:Fire triangle 1565: 1563: 1560: 1558: 1555: 1553: 1550: 1548: 1545: 1543: 1540: 1538: 1535: 1533: 1530: 1528: 1525: 1523: 1520: 1517: 1514: 1512: 1511:Conflagration 1509: 1507: 1504: 1502: 1499: 1496: 1493: 1491: 1488: 1487: 1485: 1481: 1477: 1470: 1465: 1463: 1458: 1456: 1451: 1450: 1447: 1441: 1438: 1437: 1418: 1414: 1408: 1393: 1386: 1379: 1370: 1354: 1350: 1344: 1335: 1326: 1318: 1314: 1307: 1298: 1289: 1273: 1267: 1251: 1247: 1243: 1237: 1230: 1224: 1208: 1204: 1198: 1182: 1178: 1172: 1164: 1160: 1156: 1149: 1132: 1128: 1122: 1106: 1102: 1095: 1093: 1085: 1082: 1078: 1074: 1068: 1061: 1055: 1048: 1042: 1033: 1031: 1022: 1020:9780440508274 1016: 1012: 1011: 1002: 986: 982: 975: 959: 955: 949: 945: 935: 932: 930: 927: 925: 922: 920: 917: 915: 912: 910: 907: 905: 902: 900: 897: 895: 892: 891: 884: 882: 877: 874: 870: 865: 863: 858: 855: 850: 841: 837: 835: 831: 825: 821: 818: 812: 810: 806: 802: 798: 793: 789: 785: 781: 772: 768: 761: 753: 742: 737: 736: 727: 724: 723: 714: 711: 710: 701: 698: 697: 690: 687: 686: 677: 674: 673: 664: 661: 660: 656: 653: 652: 649: 641: 633: 630: 620: 616: 607: 605: 595: 593: 589: 585: 575: 571: 567: 564: 562: 552: 550: 547:, or optical 546: 542: 536: 532: 520: 516: 512: 508: 503: 498: 494: 493: 488: 481: 476: 472: 469: 466: 461: 458: 457: 456: 453: 451: 446: 443: 437: 435: 429: 427: 417: 408: 404: 402: 397: 384: 375: 371: 367: 365: 364:fusible alloy 356: 347: 343: 341: 335: 333: 329: 325: 314: 310: 306: 304: 300: 295: 292: 285:United States 277: 275: 271: 267: 266:nursing homes 263: 259: 255: 250: 248: 237: 235: 229: 227: 222: 220: 216: 212: 200: 196: 192: 187: 185: 181: 178: 173: 163: 159: 157: 153: 149: 141: 137: 132: 128: 124: 113: 110: 102: 91: 88: 84: 81: 77: 74: 70: 67: 63: 60: –  59: 55: 54:Find sources: 48: 44: 38: 37: 32:This article 30: 26: 21: 20: 2342: 2330: 2229:Flame spread 2115:Fireproofing 2093:and services 1994:Smoke damper 1984:Safety glass 1919:Fire hydrant 1884:Fire curtain 1844:Booster pump 1803:Relief valve 1767:Fusible link 1736: 1557:Fire loading 1552:Fire control 1522:Deflagration 1420:. Retrieved 1417:www.nfpa.org 1416: 1407: 1395:. Retrieved 1391: 1378: 1369: 1357:. Retrieved 1352: 1343: 1334: 1325: 1316: 1306: 1297: 1288: 1276:. Retrieved 1266: 1254:. Retrieved 1245: 1236: 1223: 1211:. Retrieved 1197: 1185:. Retrieved 1171: 1158: 1148: 1135:. Retrieved 1121: 1109:. Retrieved 1105:the original 1067: 1054: 1041: 1009: 1001: 989:. Retrieved 974: 962:. Retrieved 948: 924:Pipe support 878: 866: 859: 851: 847: 838: 830:technologist 826: 822: 813: 804: 800: 797:firefighters 788:Control mode 787: 783: 779: 777: 766: 755: 648:inside bulb 647: 643:Temperature 626: 617: 613: 601: 581: 572: 568: 565: 558: 537: 533: 530: 515:dry nitrogen 454: 447: 438: 430: 422: 405: 398: 394: 372: 368: 361: 344: 339: 336: 320: 311: 307: 296: 288: 251: 247:firefighters 243: 230: 223: 213: 188: 182: 175: 160: 147: 145: 127: 105: 96: 86: 79: 72: 65: 53: 41:Please help 36:verification 33: 1949:Grease duct 1904:Fire escape 1894:Fire damper 1787:Intumescent 1732:Fire safety 1697:Fire bucket 1592:Flash point 1422:15 November 1397:15 November 1278:29 November 629:gate valves 598:Water spray 434:check valve 280:Regulations 270:dormitories 226:occupancies 2380:Hydraulics 2359:Categories 2246:(NFPA 101) 2209:CE marking 2062:Fire drill 1665:Technology 1562:Fire point 1547:Fire class 1527:Detonation 1137:22 January 964:6 February 941:References 873:flash fire 786:the fire. 610:Water mist 578:Foam water 555:Pre-action 495:Increased 401:antifreeze 170:See also: 99:March 2023 69:newspapers 2202:Standards 2131:Fire test 1959:Occupancy 1924:Fire pump 1914:Fire hose 1899:Fire door 1879:Exit sign 1854:Crash bar 1627:Pyrolysis 1622:Pool fire 1587:Flashover 1542:Explosive 1490:Backdraft 1111:11 August 934:Victaulic 869:explosion 836:(NICET). 497:corrosion 350:Operation 274:hospitals 217:improved 199:hogsheads 2385:Plumbing 2331:Category 2295:See also 2224:EN 16034 1934:Firestop 1889:Fire cut 1612:Jet fire 1602:Gas leak 1518:(HAZMAT) 1501:Boilover 1329:NFPA 750 1256:4 August 1250:Archived 1246:BBC News 1207:Archived 1181:Archived 1163:Archived 1131:Archived 1077:Archived 991:15 March 985:Archived 983:. NFPA. 958:Archived 887:See also 784:suppress 411:Dry pipe 391:Wet pipe 303:de facto 2343:Commons 2176:(NCEES) 1497:(BLEVE) 854:hydrant 780:control 732:Purple 694:Yellow 669:Orange 592:hangars 561:museums 206:⁄ 166:History 83:scholar 2390:Piping 2274:Awards 2188:(SFPE) 2182:(NFPA) 2164:(FEMA) 2127:(FSES) 1359:20 May 1213:8 July 1187:8 July 1086:, 1996 1017:  749:Black 706:Green 636:Design 623:Valves 527:Deluge 507:copper 502:oxygen 317:Europe 272:, and 262:hotels 150:is an 85:  78:  71:  64:  56:  2265:UL 94 2219:EN 54 2170:(IFE) 1799:(PPE) 1388:(PDF) 719:Blue 604:BLEVE 378:Types 240:Usage 90:JSTOR 76:books 2214:EN 3 2194:(UL) 1424:2019 1399:2019 1361:2023 1280:2018 1258:2011 1215:2015 1189:2015 1139:2015 1113:2006 1084:NFPA 1015:ISBN 993:2016 966:2013 809:ESFR 682:Red 584:foam 62:news 871:or 745:500 743:440 740:260 738:227 728:360 725:182 715:286 712:141 702:200 691:174 678:155 665:135 657:°F 509:or 45:by 2361:: 1415:. 1390:. 1351:. 1315:. 1244:. 1205:. 1179:. 1161:. 1157:. 1129:. 1091:^ 1075:" 1029:^ 883:. 799:. 699:93 688:79 675:68 662:57 654:°C 594:. 543:, 268:, 264:, 236:. 146:A 1468:e 1461:t 1454:v 1426:. 1401:. 1363:. 1319:. 1282:. 1260:. 1217:. 1191:. 1141:. 1115:. 1023:. 995:. 968:. 807:( 208:2 204:1 142:. 125:. 112:) 106:( 101:) 97:( 87:· 80:· 73:· 66:· 39:.

Index


verification
improve this article
adding citations to reliable sources
"Fire sprinkler system"
news
newspapers
books
scholar
JSTOR
Learn how and when to remove this message
Fire sprinkler

sprinkler head
red liquid in the glass bulb
active fire protection
fire sprinklers
Fire sprinkler
Leonardo da Vinci
Ambrose Godfrey
Theatre Royal, Drury Lane
William Congreve
hogsheads
Frederick Grinnell
Henry S. Parmalee
occupancies
British Automatic Fire Sprinkler Association
firefighters
building codes
insurance companies